cGas Detector Analog Transmitter - Operation Manual
Rev. B | 2020.07
Signal output and supply should be in shielded cable. The cable shield should
be connected to earth ground at the controller/power supply that is providing
power for the cGas.
If the cGas Detector is being connected to either a QCC or FCS the supply
voltage will either be supplied by the QCC or FCS and any additional power
requirements of the system will be supplied by RPS-24VDC Remote Power
Supply devices. In an analog configuration, a dedicated 4-20 mA signal wire is
connected to each transmitter and only the ground and power wires are daisy
chained.
CGAS-A Connected to an FCS or QCC Controller (3-wire VDC)
If the cGas Detector is being connected to a BAS, DDC or other control panel
then either a 24 VDC power supply or 24 VAC Class 2 or better transformer
need to be used.
In all cases the voltage supply to the cGas Detector should never drop below 16