Procedure
1. In the base rack and each storage rack, connect a QSFP+ data cable to the lower 40G0 switch , and then to
the customer core switch.
2. In the base rack and each storage rack, connect a QSFP+ data cable to the upper 40G1 switch, and then to
the customer core switch.
3. In each storage rack of a multi-rack system, connect a Cat 5/6 Ethernet cable to the lower Ethernet switch
(SW0) (available ports listed above). Connect the other end of the cable to the lower Ethernet switch (SW0) in
the base rack.
4. In each storage rack of a multi-rack system, connect a Cat 5/6 Ethernet cable to the upper Ethernet switch
(SW1) (available ports listed above). Connect the other end of the cable to the upper Ethernet switch (SW1)
in the base rack.
5. In the base rack, connect a Cat 5/6 Ethernet cable from the NIC card, SMU node 0, Port 4 to the local
network.
6. In the base rack, connect another Cat 5/6 Ethernet cable from the NIC card, SMU node 1, Port 4 to the local
network.
11.4 Cable SMU and 36-Port 40GbE LDN with Dual 48-Port LMN
Switches
About this task
For ClusterStor L300 and L300N inter-rack 40GbE 36-port LDN switch cabling, the available uplink ports are:
●
Upper switch 1 (40GS1) - ports 2, 4, and all odd-numbered ports
●
Lower switch 0 (40G0) - ports 2, 4, and all odd-numbered ports
For inter-rack Ethernet switch cabling, the available uplink ports in the base rack are:
●
Upper switch 1 (SW1) - ports 1 through 24, 29, 31, 41, and 43
●
Lower switch 0 (SW0) - ports 1 through 24, 29, 31, 41, and 43
●
Port 37 is the ISL and is not available.
For inter-rack Ethernet switch cabling, the available uplink ports in the storage rack (24-port switches) are:
●
Upper switch 1 (SW1) - 5, 7, 17, and 19
●
Lower switch 0 (SW0) - 5, 7, 17, and 19
●
Port 13 is the ISL and is not available
IMPORTANT: Switch port assignments in the configuration diagrams are provided for reference only. For
system-specific inter-rack switch cabling, refer to the system-specific storage configuration document
(SCD).
Environment Connections
43