Hybrid current input and binary input/output module
IC-NT CT-BIO7 is optional plug-in card. Through this card controller can accommodate one AC
current (CT) measuring input and up to 7 binary inputs or outputs. In LiteEdit PC configuration tool
(version 4.4 and higher) it is possible to easily choose if particular I/O will be binary input or output.
To insert the module, you must open the cover first (use screwdriver to open) and then insert the
module into slot. Once you have inserted it, the module will snap under plastic teeth. It is supposed to
be installed permanently. Should you need to remove it, the safest way is to remove whole back cover
and then remove module manually. Installing IC-NT CT-BIO7 module is similar to installing RS 232
module. The difference is that module fits to “extension module” slot and after installing IC-NT CT-
BIO7 you do not put back the small cover.
Hint:
or in
IL-NT RD Remote display software
IL-NT RD is remote display software for a controller. Remote display provides the same control and
monitoring functions as controller itself. Remote display for IL-NT controllers uses standard IL-NT
controller with Remote display software. No further programing of the display is required
– unit is self-
configurable from the main controller. It is connected with the controller via IL-NT-RS232
communication modules using RS232 line. Longer distances (up to 1200m) are possible using IL-NT-
RS232-485 communication module or when RS232/RS485 converters are used.
The IL-NT RD hardware type should fit to the master IL-NT.
Hint:
IL-NT-RD Remote display software
Remote annunciator IGL - RA15
The remote annunciator IGL-RA15 can be connected to the IL-NT unit via CAN bus. Any of the binary
outputs can be configured (using LiteEdit software) to each LED diode on the RA15. The module can
be also enabled or disabled using LiteEdit software.
If IGL-RA15 remote annunciator is not communicating with a controller via CAN bus, it activates a
warning.
Hint:
For connection details please refer to chapter
Extension modules (CAN bus) connection
Please see the documentation of RA15 for the technical and function description.