InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 77
IL-NT-AMF-2.2-Reference Guide.pdf
Hint:
This setpoint have to be set properly to correct evaluation of Fuel Theft.
MaxFuelDrop
[%/h]
Setpoint indicates the maximum allowable drop of fuel in fuel tank per running hour. When the engine
is not running the maximal allowed fuel drop-off is preset to 5% of total tank volume per hour.
In case of detection of theft/leak the alarm "Wrn FuelTheft" is raised and same alarm is send via SMS
and displayed by WebSupervisor (if used).
Step:
1
Range:
0
– 50%
Hint:
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.
Engine Protect
ProtectHoldOff
[s]
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the
ProtectHoldOff
time. The time starts after reaching
Starting
RPM
.
Step:
1s
Range:
0
– 300 s
Hint:
The protections sequence diagram can be found in
in chapter
displays when and what protections are active.
Horn Timeout
[s]
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout
starts again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Step:
1s
Range:
0
– 600 s
Overspeed Sd
[%]
Threshold for over speed protection
Step:
1% of nominal RPM
Range:
100
– 150%
Hint:
The Overspeed protection value is increasing by 1
0% of “Overspeed Sd” setpoint, e.g. from default
115 % to 125% of nominal RPM for the duration of 5sec (ProtectHoldOff delay). ProtectHoldOff delay
takes place during the start of the gen-set when some engine protections have to be blocked. This
delay starts after reaching 25% of nominal RPM. It holds true if the value Gear Teeth = 0.
AI1 Wrn
[ Bar]
Warning threshold level for ANALOG INPUT 1
Step:
0,1 bar
Range: -10
– 1000
AI1 Sd
[ Bar]
Shutdown threshold level for ANALOG INPUT 1
Step:
0,1 bar
Range: -10
– 1000
AI1 Del
[s]
Delay for ANALOG INPUT 1