InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 142
IL-NT-AMF-2.2-Reference Guide.pdf
Analog inputs
Not electrically separated
Number of inputs
3
Resolution
10 bits
Maximal resistance range
2500
Resistance measurement tolerance
2 %
2
out of measured value
Speed pick-up input
Type of sensor
magnetic pick-up (connection by shielded
cable is recommended)
Minimum input voltage
2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage
50 Veff
Minimum measured frequency
4 Hz
Maximum measured frequency
10 kHz (min. input voltage 6Vpk-pk)
Frequency measurement tolerance
0,2 %
D+ Function
Max. D+ output current
250 mA
Guaranteed level for signal Charging OK
80% of supply voltage
*CAN bus interface
Not electrically separated
Maximal CAN bus length
200m
Speed
250kBd
Nominal impedance
120
Cable type
twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length
and 32 iS-COM units connected:
Nominal Velocity of Propagation
min. 75% (max. 4,4 ns/m)
Wire crosscut
min.0,25 mm
2
Maximal attenuation (at 1 MHz)
2 dB / 100m
Recommended Industrial Automation & Process Control Cables:
BELDEN (see
3082A DeviceBus for Allen-Bradley DeviceNet
3083A DeviceBus for Allen-Bradley DeviceNet
3086A DeviceBus for Honeywell SDS
3087A DeviceBus for Honeywell SDS
3084A DeviceBus for Allen-Bradley DeviceNet
3085A DeviceBus for Allen-Bradley DeviceNet
3105A Paired EIA Industrial RS485 cable
Unitronic BUS DeviceNet Trunk Cable
Unitronic BUS DeviceNet Drop Cable
Unitronic BUS CAN
Unitronic-FD BUS P CAN UL/CSA