InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 110
IL-NT-AMF-2.2-Reference Guide.pdf
Electric state machine
MainsOper
Mains is present and all its values are within limits.
(MCB is closed, GCB is opened)
MainsFlt
Mains cut off
– immediate state
MainsFlt
Mains cut off
– takes EmergStart del
IslOper
Island operation (MCB is opened, GCB is closed)
MainsRet
Mains recover
Brks Off
GCB, MCB opened
MinStabTO
Minimal Stabilization Timeout for electric protections
MaxStabTO
Maximal Stabilization Timeout for electric protections
Trans Del
Forward return break delay. Delay between GCB opening and MCB closing
List of possible events
Events specification
Protection
type
Information on binary
output available (See
Description
AI1 Wrn
WRN
YES
Value measured on analog input 1 is
lower than
AI1 Wrn
setpoint.
AI1 Sd
SD
YES
Value measured on analog input 1 is
lower than
AI1 Sd
setpoint.
AI2 Wrn
WRN
YES
Value measured on analog input 2 is
greater than
AI2 Wrn
setpoint.
AI2 Sd
SD
YES
Value measured on analog input 2 is
greater than
AI2 Sd
setpoint.
AI3 Wrn
WRN
YES
Value measured on analog input 3 is
greater than
AI3 Wrn
setpoint.
AI3 Sd
SD
YES
Value measured on analog input 3 is
greater than
AI3 Sd
setpoint.
IOM AIx Wrn
WRN
YES
Warning alarm configurable on the
input of IG-IOM/IGS-PTM.
IOM AIx Sd
SD
YES
Shutdown alarm configurable on the
input of IG-IOM/IGS-PTM.
Binary input
Configurable
YES
Configurable Warning/BOC/Shutdown
alarms on the inputs of IL-NT.
IOM Bin Inp
Configurable
YES
Configurable Warning/BOC/Shutdown
alarms on the inputs of IG-IOM/IGS-
PTM.
IL-NT-BIO8
Configurable
YES
Configurable Warning/BOC/Shutdown
alarms on the inputs of IL-NT-BIO8.
ActCallCH1Fail
WRN
NO
Active call on channel 1 failed.
ActCallCH2Fail
WRN
NO
Active call on channel 2 failed.
Low BackupBatt
WRN
NO
RTC backup battery is flat
Wrn Batt Volt
WRN
YES
Battery voltage is out of limits given by
Batt Undervolt/Batt OverVolt
setpoints.
ChargeAlt Fail
WRN
YES
Failure of alternator for charging the
battery.
Sd BatteryFlat
SD
YES
If the controller switches off during
starting sequence due to bad battery
c
ondition it doesn’t try to start again
and activates this protection.
Sd Start Fail
SD
YES
Gen-set start failed. All crank attempts
were tried without success.
Wrn Stop Fail
WRN
YES
Gen-set stop failed. See description at
Sd Gen Lx >V
SD
YES
The generator voltage is out of limits