ECU SpeedAdj
[ % ]
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%.
Step:
1%
Range:
0
– 100%
Hint:
The minimum value 0% is equal to 90% of nominal speed. Maximum value 100% is equal to 110% of
nominal speed.
Fuel Pump ON
[%]
When the actual value of Fuel Level is lower or equals to this value then the binary output Fuel Pump
is activated.
Step:
1
Range:
0
– 100 %
Fuel Pump OFF
[%]
When the actual value of Fuel Level is higher or equals to this value then the binary output Fuel Pump
is deactivated.
Step:
1
Range:
0
– 100 %
Hint:
The two setpoints above are compared to Analog Input 3 (usually used for Fuel Level)
It is a prerequisite for this function to use a fuel level sensor at this analog input.
TempSwitch ON
[-]
Threshold level for switching on the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step:
1
Range:
-100 .. 10000 [-]
TempSwitchOFF
[-]
Threshold level for switching off the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step:
1
Range:
-100 .. 10000 [-]
Hint:
The description of Power Switch function is in chapter
PowerSwitch ON
[kW]
Threshold level for switching the binary output “Power Switch” on.
Step:
1
Range:
0
– 32000 kW
PowerSwitchOFF
[kW]
Threshold level for switching
the binary output “Power Switch” off.
Step:
1
Range:
0
– 32000 kW
Hint:
The description of Power Switch function is in chapter
FuelTankVolume
[l]
Define a capacity of Genset fuel tank.
Step:
1
Range:
1
– 10000l