Switchboard lighting strike protection according standard regulation is expected
for all 4 connection
types!!!
Hint:
Phase sequence check is not possible to evaluate under voltage 50V what causes that if measured
voltage 50V is within the allowed range, controller will not allow to close the GCB, even if relevant LED
diode on front panel of IL-NT lits.
Analog inputs
Three analog inputs are available on the IL-NT. First analog input is fixed to be used for engine Oil
Pressure.
Configuration
Each analog input can be configured by LiteEdit software in following way (First analog input is
dedicated to engine Oil pressure).
Analog input item
LiteEdit
Possibility
Type
Type
Not used
Alarm
Monitoring
Analog input isn’t used
Analog is measured and used
for protection
Analog is only measured and
not used for protection
Analog input name
Name
Up to 14 ASCII characters
Config of input
Config
Analog
Binary (not supp. by PTM)
Tri-state (not supp. by PTM)
ECU
Analog measuring in specified
range.
Binary: open/close - threshold
750
.
Three-state: open/close -
threshold 750
,
Failure <10
or > 2400
Value is read from ECU
Physical dimension
Dim
bar,%,°C, …
Up to 4 ASCII characters
(Valid only for analog inputs)
Polarity
Contact type NC
NO
Valid only for binary and three-
state inputs
Valid only for binary and three-
state inputs
Protection direction
Protection
Over
Overstep. Sensor Fail does
not activate protection.
Over+Fls
Overstep and Sensor Fail
activates protection.
Under
Under step. Sensor Fail does
not activate protection.
Under+Fls
Under step and Sensor Fail
activates protection.
Sensor characteristic Sensor
Predefined user curves
User changeable and
configurable
Resolution
Resolution
0
– 0,00001
Sensor resolution
(Valid only for analog inputs)
Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and
delay adjust in
Extension I/O
and
Engine Protect
group.
Hint:
Description of Sensor fail evaluation can be found in chapter
, article