InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 59
IL-NT-AMF-2.2-Reference Guide.pdf
Power Switch
This switch is assigned to the gen-set active power. The setpoints
for on and off level adjustment are located in the setpoint group
. Typical usage for this binary output can be switching of dummy load. The output behaves
based on the setpoint adjustment as described on picture lower:
Hint:
Power switch function and corresponding binary output is activated 30s after the engine is running.
Maintenance
Output closes if the Maintenance alarm activates, i.e. the gen-set has been running for more than
Engine Protect
: Wrn
Maintenance
.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Ctrl HeartBeat
Output signalizes Watchdog Reset. In a healthy state it blinks at 500ms : 500ms rate. When Watchdog
Reset occurs, it stops blinking.
DualAMFCtrlOut
Control output for Mutual Standby Application. This binary output of controller 1 must be configured
and interconnected with binary input
of controller 2 for correct Mutual Standby function
Mode OFF
The output is closed, if OFF Mode is selected.