5
Function setting
BIT15
Reserved
BIT14
Reserved
BIT13
1: curve setting enable; 0: curve setting disable
(Zone2)
BIT12
1: curve setting enable; 0: curve setting disable
(Zone1)
BIT11
DHW pump's running constant-temperature water
recycling
BIT10
ECO mode
BIT9
Reserved
BIT8
Holiday home (the status can only be read, not
changed)
BIT7
0: Silent mode level1;
1: Silent mode level2
BIT6 :
Silent mode
BIT5 :
Holiday away (the status can only be read, but
cannot be changed)
BIT4 :
Disinfect
BIT3 :
Reserved
BIT2 :
Reserved
BIT1 :
Reserved
BIT0 :
Reserved
6
Curve selection
Bit15-Bit8: Zone 2 curve 1-9
Bit0-Bit7: Zone 1 curve 1-9
7
Forced water heating
0 : invalid
1 : Forced on
2 : Forced off
TBH is electric heating for making hot water tank.
IBH is the electric heating behind the hydraulic
module.
TBH and IBH cannot be forced together
8
Forced TBH
9
Forced IBH1
10
SG running time
0-24hrs
Note: Explanation of the T1s range of the floor heating set temperature:
Cooling mode T1S low temperature setting, range: 5-25°C
Cooling mode T1S high temperature setting, range: 18-25°C
Prepared heat mode T1S low-temperature setting, range: 25-55°C;
Prepared heat mode T1S temperature setting, range: 35-60°C.