216
T4DHWmin
Default: - 25°C, the range of - 25 -5°C, adjusted spacing 1°C
217
t_TBH_delay
Default: 30 min Range: 0~240min ; adjustment interval 5min
218
dT5S_TBH_off
Default: 5°C, range: 0 ~ 10°C, adjustment interval 1°C
219
T4_TBH_on
Default: 5°C, range: -5~20°C, adjustment interval 1°C
220
T5s_ DI
Sterilization function water tank set temperature, setting range 60~70°C, default 65°
C
221
t_ DI _max
Maximum value of sterilization cycle, setting range: 90~ 300 min , default 210 min ,
222
t_ DI _hightemp
Sterilization high temperature time, setting range: 5~ 60 min , default 15min
223
t_interval_C
Cooling mode compressor start time interval; range: 5~ 5 min , default value is 5min
224
dT1SC
Default: 5°C, range: 2-10°C, adjustment interval 1°C
225
dTSC
Default: 2°C, range: 1-10°C, adjustment interval 1°C
226
T4cmax
Default: 52°C, range: 35- 52°C; adjustment interval 1°C
227
T4cmin
Default: -5°C, range: -5-25°C; adjustment interval 1°C
228
t_interval_H
System heating mode compressor start interval; range: . 5 ~ . 5 min , the default
value . 5 min
229
dT1SH
Default: 5°C, range: 2-10°C, adjustment interval 1°C
230
dTSH
Default: 2°C, range: 1-10°C, adjustment interval 1°C
231
T4hmax
Default: 25°C, range: 20-35°C, adjustment interval 1°C
232
T4hmin
Default: - 25°C, range: -25 - 15°C, adjusted spacing . 1°C
233
T4_IBH_on
Ambient temperature of IBH for electric auxiliary heating of hydraulic module , setting
range: -15~10°C, default value: -5°C
234
dT1_IBH_on
Hydraulic module electric auxiliary heating IBH opening temperature hysteresis,
setting range: 2~10°C, default value 5°C
235
t_IBH_delay
Hydraulic module electric auxiliary heating IBH delay opening time, setting range:
15~120min , default value 30min
236
t_IBH12_delay
After the hydraulic IBH1 is turned on, the IBH2 is turned on delay time, the setting
range: 5~30min , the default value is 5min, reserved to query the register and report
the address error
237
T4_AHS_on
The external heat source AHS turns on the ambient temperature, the setting range is
-15~10°C, the default value is -5°C
238
dT1_AHS_on
External heat source AHS opening temperature hysteresis, setting range: 2~10°C,
default value 5°C
239
dT1_AHS_off
External heat source AHS shutdown temperature hysteresis, setting range: -5~0°C,
the default value is 0°C reserved to query the address error reported by this register
240
t_AHS_delay
External heat source AHS lag opening time, setting range 5~120min , default value
30min.
241
t_DHWHP_max
Hot water system heat pump operation the maximum time setting range: 10 ~ 600
min ; Default: 90 min ; setting value minutes
242
t_DHWHP_restrict
The heat pump limits the time for running hot water, the setting range: 10~600 min ;
the default value: 3 0min ; the setting value is minutes
243
T4autocmin
The default value is: 25°C, the range is: 20~29°C, the adjustment interval is 1°C
244
T4autohmax
The default value is: 17°C, the range is: 10~17°C, the adjustment interval is 1°C
245
T1S_H. A _H
During vacation, the setting value of T1 in heating mode , range: 20~25°C, default
25°C
246
T5S_H. A _DHW
During vacation, T1 setting value in hot water mode , range: 20~25°C, default 25°C
247
Startup percentage
Range 10-100 , default 10. Adjustment interval 10
248
Adjustment time
Range 1-60 Default 5
249
--
--
250
IBH1 power
Range 0-200 , default 0 , unit 100W
251
IBH2 power
Range 0-200 , default 0 , unit 100W