Code
State
Default Min
max
setting
interval
unit
15.1
CN12 ON/OFF
Define the CN12 port,0= REMOTE ON/OFF,1= TBH ON/OFF
2= AHS ON/OFF
0
0
1
1
/
15.2
SMART GRID
Enable or disable the SMART GRID. 0=NON
;
1=YES
0
0
1
1
/
15.3
T1b (Tw2)
Enable or disable the T1b (Tw2)
0=NON,1=YES
0
0
1
1
/
15.4
Tbt1
Enable or disable the Tbt1;
0=NON,1=YES
0
0
1
1
/
15.6
Ta
Enable or disable the Ta;
0=NON,1=YES
0
0
1
1
/
15.7
Ta-adj
The corrected value of Ta on wired controller
-2
-10
1
1
°C
15.8
SOLAR INPUT
Choose the SOLAR INPUT;
0=NON,1=CN18Tsolar,2=CN11SL1SL2
0
0
2
1
/
15.9
F-PIPE LENGTH
Choose the total length of the liquid pipe(F-PIPE
LENGTH);
0
0
1
1
/
15.10
RT/Ta_PCB
Enable or disable the RT/Ta_PCB;
0=NON,1=YES
0
0
1
1
/
15.11 PUMPI SILENT MODE Enable or disable PUMPI SILENT MODE 0=NON, 1=YES
0
0
1
1
/
16.1
PER_START
Start-up percentage of multiple units
10
10
100
10
%
16.2
TIME_ADJUST
Adjustment time of adding and subtracting units
10
0
60
1
MIN
16.3
ADDRESS RESET Reset the address code of the unit
FF
FF
+0
-F
1
/
17.1
HMI SET
Choose the HMI;
0=MASTER,1=SLAVE
0
0
1
1
/
17.2
HMI ADDRESS FOR
BMS
Set the HMI address code for BMS
0
0
15