15 -
General technical data
Performance
SIZE
81
91
101
121
141
Power supply
400/50/3+N
RADIANT PANELS
Heating
Heating capacity (EN 14511:2018)
1,9
kW
16,3
18,0
22,0
26,0
30,1
Total power input (EN 14511:2018)
1
kW
3,63
3,83
5,00
6,37
7,70
COP (EN 14511:2018)
2
4,49
4,70
4,40
4,08
3,91
ErP Space Heating Energy Class -
AVERAGE Climate - W35
8,11
A++
A+++
A+++
A+++
A++
SCOP - AVERAGE Climate - W35
10
4,30
4,60
4,53
4,50
4,19
Cooling
Cooling capacity (EN 14511:2018)
5,9 kW
15,5
18,5
23,0
27,0
31,0
Total power input (EN 14511:2018)
5
kW
3,63
3,90
5,00
6,28
7,75
EER (EN 14511:2013)
6
4,27
4,75
4,60
4,30
4,00
Water flow-rate
5
l/s
0,74
0,88
1,10
1,29
1,48
Useful pump discharge head
5
kPa
19,6
99,5
89,4
74,4
54,0
TERMINAL UNIT
Heating
Heating capacity (EN 14511:2018)
3
kW
16,2
18,0
22,0
26,0
30,0
Total power input (EN 14511:2018)
3
kW
4,70
5,14
6,47
8,39
10,3
COP (EN 14511:2018)
2
3,45
3,50
3,40
3,10
2,90
Cooling
Cooling capacity (EN 14511:2018)
7
kW
13,8
17,0
21,0
26,0
29,5
Total power input (EN 14511:2018)
7
kW
5,19
5,57
7,12
9,63
11,6
EER (EN 14511:2018)
6
2,66
3,05
2,95
2,70
2,55
SEER
10
4,54
4,70
4,70
4,66
4,49
Water flow-rate
7
l/s
0,66
0,81
1,00
1,05
1,10
Useful pump discharge head
7
kPa
30,7
102
94,6
78,8
59,4
RADIATORS
Heating
Heating capacity (EN 14511:2018)
4
kW
16,1
18,0
22,0
26,0
30,0
Total power input (EN 14511:2018)
4
kW
5,83
6,55
8,30
10,61
13,0
COP (EN 14511:2018)
2
2,76
2,75
2,65
2,45
2,30
ErP Space Heating Energy Class -
AVERAGE Climate - W55
8
A++
A++
A++
A+
A+
SCOP - AVERAGE Climate - W55
10
3,27
3,21
3,22
3,14
3,14
Water flow-rate
4
l/s
0,48
0,54
0,66
0,78
0,90
Useful pump discharge head
4
kPa
55,5
109
106
103
99,1
The Product is compliant with the Erp (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 811/2013 (rate heat output ≤70 kW at
specified reference conditions) and the Commission delegated Regulation (EU) No 813/2013 (rated heat output ≤400 kW at specified reference conditions).
‘Contains fluorinated greenhouse gases’(GWP 675).
1. Entering/leaving water temperature user side 30/35 °C, Entering external exchanger
air temperature 7 °C (R.H. = 85%).
2. COP (EN 14511:2018) Heating performance coefficient. Ratio between delivered
heating capacitu and power input in compliance with EN 14511:2018.
3. Entering/leaving water temperature user side 40/45 °C, Entering external exchanger
air temperature 7 °C (R.H. = 85%).
4. Entering/leaving water temperature user side 47/55 °C, Entering external exchanger
air temperature7 °C (R.H. = 85%).
5. Entering/leaving water temperature user side 23/18 °C, Entering external exchanger
air temperature 35 °C.
6. EER (EN 14511:2018) cooling performance coefficient. Ratio between delivered
coolimg capacitu and power input in compliance with EN 14511:2018.
7. User side entering/leaving water temperature 12/7 °C, external exchanger entering
air 35°C.
8. Seasonal Space Heating Energy Efficiency Class according to Commission delega-
ted Regulation (EU) No 811/2013. W = Water outlet temperature (°C).
9. Data referred to unit operation with inverter frequency optimized for this application.
10. Data calculated according to the EN 14825:2016 Regulation.
121