Cod
Description
Cause
Remendy
Pump
status
E04
Mains undervoltage
Power supply too low on mains side
Check mains voltage.
OFF
E05
Mains overvoltage
Power supply too high on mains side Check mains voltage.
OFF
E07
Generator operation
Pump hydraulics have fluid running
through them.
Check the system
ON
E09
Turbine operation
The pump is driven in reverse
Check flow, install non-return valves
if necessary
OFF
E10
Blocking
The rotor is blocked
Request customer service
OFF
E11
Dry running
Air in the pump
Check system charge (pressure and
volume)
ON
E21
Overload
Sluggish motor
Request customer service
ON
E23
Short-circuit
Motor current too high
Request customer service
OFF
E25
Contacting/winding
Defective
Request customer service
OFF
E30
Module overheated
Check operating conditions
OFF
E31
Overheated power section
Ambient temperature too high
Check operating conditions
OFF
E36
Electronic faults
Request customer service
OFF