Admissible water flow rates
SIZE
81
91
101
121
141
Minimum flow-rate
Qmin
[l/s]
0,48
0,54
0,66
0,78
0,90
Maximum flow-rate
Qmin
[l/s]
0,92
1,03
1,26
1,49
1,72
Fouling Correction Factors
Internal exchanger
m²C/W
F1
FK1
0,44x10 (-4)
1
1
0,88x10 (-4)
0,96
0,99
1,76x10 (-4)
0,93
0,98
The cooling performance values provided in the tables are based on the external exchanger having clean plates (fouling factor 1). For different fouling factor values, multiply the
performance by the coefficients shown in the table.
F1 = Cooling capacity correction factors
FK1 = Compressor power input correction factor
General technical data