Method B
On-Off from input H - L1
Heat-Cool from user interface
User interface setting:
ROOM THERMOSTAT and ROOM THERMOSTAT to ONE ZONE,
There are three methods for connecting the thermostat cable and it depends on the application.
NOTE
When ROOM THERMOSTAT is set , the indoor temperature sensor Ta can’t be set to valid, unit running only according to T1.
NOTE
The wiring of the thermostat should correspond to the settings of the user interface.
See chapter START-UP AND CONFIGURATION - ROOM THERMOSTAT.
Power supply of machine and room thermostat must be connected to the same Neutral Line and (L2) Phase Line(for 3-phase unit
only).
Method A
On-Off + Heat from input H - L1
On-Off + Cool from input C - L1
User interface setting:
ROOM THERMOSTAT and ROOM THERMOSTAT to MODE SET
CN11
CN11
Method C
Hydraulic module is connected with two external temperature..
On-Off zone 1 from input H - L1
On-Off zone 1 from input C - L1
Heat-Cool from user interface
User interface setting:
ROOM THERMOSTAT and ROOM THERMOSTAT to DOUBLE ZONE
CN11