138
Water flow
Actual value *100 unit: M3/H
139
External unit frequency
limiting scheme
Solution value ----- external unit feedback 174
140
Hydraulic module capacity
value
Actual value *100 unit: Kw
141
Solar sensor temperature
142
Unit online number infor-
mation
BIT1-BIT15 respectively represent the online status of slaves 1-15
BIT0 reservation
143
High battery value
144
Low battery value
145
High calorific value
146
Low calorific value
200-208 are read-only registers; cannot be set, 209-
Register
address
Data content
Remarks
200
Appliance type
The upper 8 digits are the types of household appliances:
Central heating: 0x07
The middle three are product algebra
First generation: 0
Second generation: 1
The lower 4 bits are subtypes
R32 refrigerant medium frequency water pump model: 0x02
201
T1S cooling set temperature
The lower 8 bits are area 1 and the upper 8 bits are area 2
202
T1S cooling set temperature
The lower 8 bits are area 1 and the upper 8 bits are area 2
203
T1S heating set tempera-
The lower 8 bits are area 1 and the upper 8 bits are area 2
204
T1S heating set lower tem-
The lower 8 bits are area 1 and the upper 8 bits are area 2
205
TS set upper temperature
Actual value *2
206
TS set temperature lower
Actual value *2
207
Upper limit of set tempera-
208
Lower limit of set tempera-
209
PUMP RUNNING TIME
DHW PUMP backwater running time, the default is 5 minutes, the adjustment range
is 5 ~ 120min , the adjustment interval is 1min