1011
T1
Total outlet temperature, unit: °C. Send value = actual value invalid value
0x7F
1012
T1B
Total water output of the system (after auxiliary heat source), unit: °C.
Send value = actual value invalid value 0x7F
1013
T2
Refrigerant liquid side temperature , unit: °C. Send value = actual value
invalid value 0x7F
1014
T2B
Temperature of refrigerant gas side , unit: °C. Send value = actual value
invalid value 0x7F
1015
T5
Water tank temperature invalid value 0x7F
1016
Ta
Room temperature, unit: °C. Send value = actual value invalid value 0x7F
1017
Tbt1
Tbt1 , unit: °C. Send value = actual value invalid value 0x7F
1018
--
--
1019
Water flow
Actual value *100 unit: M3/H
1020
model
10-18 : stands for 10-18KW ( valid for the second generation unit )
1021
Unit target frequency
1022
Unit version number
1~99 indicates the serial number of the whole machine, which refers to
the version number of the hydraulic module
1023
High calorific value
1024
Low calorific value
1025
Hydraulic module capacity
value
Actual value *100 unit: Kw
1026
Wind speed
Fan speed, unit r/min . Send value = actual speed
1027
PMV opening
External machines electronic expansion valve opening degree , the unit:
P . Send value = actual value (only display multiples of 8 )
1028
T3 temperature
Condenser temperature, unit: °C. Send value = actual value invalid value
0x7F
1029
T4 temperature
Outdoor ambient temperature, unit: °C. Send value = actual value invalid
value 0x7F
1030
Exhaust gas temperature
Compressor discharge temperature Tp , unit: °C. Send value = actual
value invalid value 0x7F
1031
Return air temperature
Compressor return air temperature, unit: °C. Send value = actual value
invalid value 0x7F
1032
TF module temperature
Unit (°C) ---- Invalid value of external feedback 0x7F
1033
Pressure value 1
High-pressure value of external machine, unit: kPA . Send value = true
value
1034
Pressure value 2
Low pressure value of external machine, unit: kPA . Sent value = true
value (reserved)
1035
DC bus current
Unit: Ampere
1036
DC bus voltage
Return value = actual value ( unit: volts)
1037
External current
External unit running current, unit A , send value = actual value
1038
External voltage
A voltage value outside the unit, unit: V . Send value = actual value
1039
External unit frequency limiting
scheme
Solution value ----- external unit feedback 174
1040
High battery value
1041
Low battery value
1042
Outdoor unit software version
The above table is the modbus mapping table information of slave 1
Unit from X ( 2-15 ) information from the mapping table unit 1 a (X-1) * 200