210
Parameter setting 1
BIT15
Enable hot water
BIT14
Support water tank electric heating TBH (read only)
BIT13
Support sterilization function
BIT12
Whether to support DHW PUMP,
1 : support;
0 : not support
BIT11
Reserved
BIT10
DHW pump supports Pipe Disinfect
BIT9
Cooling enable
BIT8
T1S cooling high / low temperature setting (read only)
Zone1
BIT7
Heating enable
BIT6 :
T1S heating high / low temperature setting (read only)
Zone 1
BIT5 :
Support T1 sensor
BIT4 :
Support room temperature sensor Ta
BIT3 :
Support room thermostat ( Room thermostat )
BIT2 :
Room thermostat MODESETTING
BIT1 :
Dual Room Thermostat ,
0 : not supported;
1 : supported
BIT0 :
0: room cooling/heating first,
1: water heating first
211
Parameter setting 2
BIT15
Support reserve heat source ( IBH ) reservation
BIT14
IBH supports heating function reservation
BIT13
IBH supports hot water function reservation
BIT12
Support AHS reservation
BIT11
AHS supports heating function reservation
BIT10
AHS supports hot water function reservation
BIT9
Support solar module reservation
BIT8
Input port definition:
0 : Remote switch
1 : DHW Heater
BIT7
Smart Grid:
0 : None
1 : Yes
BIT6 :
Tw2 sensor enable:
0 : None
1 : Yes
BIT5 :
T1S cooling high / low temperature setting area 2
BIT4 :
T1S heating high / low temperature setting area 2
BIT3 :
Dual zone setting is effective
BIT2 :
Reserved
BIT1 :
Reserved
BIT0 :
Reserved
212
dT5_On
Default: 10°C, range: 1 ~ 30°C, adjustment interval 1°C
213
dT1S5
Default: 10, range: 5- 40°C, adjustment interval 1°C
214
T _Interval_DHW
Default: 5min , range: . 5 ~ 5 min , adjustment interval 1min
215
T4DHWmax
Default: 43°C, range 35-43°C, adjustment interval 1°C