![CleaverBrooks CBLE Operation And Maintenance Manual Download Page 67](http://html1.mh-extra.com/html/cleaverbrooks/cble/cble_operation-and-maintenance-manual_2622062067.webp)
750-91 (revised 2009)
Model CB-LE Packaged Boiler Manual
4-3
4.3 — Sequence of Operation: Oil or Gas
To comply with requirements of insurance underwriters such as FM Global (Factory Mutual), XL GAP (GE GAP/
IRI), or others, additional interlock devices may be used.
4.3 — Sequence of Operation: Oil or Gas
On a combination fuel unit, the gas/oil switch must be set for the proper fuel.
The following sequence occurs with power present at the program relay (PR) input terminals and with all other
operating conditions satisfied.
4.3.1 — Pre-Purge Cycle
When the burner switch (BS) is turned “on,” and controls wired in the “limit” and “fuel valve interlock” circuits are
closed and no flame signal is present, the “blower motor start circuit” is powered energizing the blower motor
starter (BMS). The load demand light (LDL) turns on. When firing oil, the air compressor motor starter (ACMS - if
provided) is also powered. The air purge valve (APV - nos. 5 and 6 oil only) remains de-energized.
At the same time, the program relay signals the modulating damper motor (MDM) to open the air damper. The
damper begins to open and drives to its full open or high fire position. Opening the damper motor allows a flow of
purging air through the boiler prior to the ignition cycle.
On certain boilers the circuitry will include a high fire switch (HFS). The purpose of the switch is to prove that the
modulating damper motor (MDM) has driven the damper to the open position during the pre-purge cycle. In this
instance, the “high fire proving circuit” is utilized.
The controls wired into the “running interlock circuit” must be closed within 10 seconds after the start sequence.
In the event any of the controls are not closed at this time, or if they subsequently open, the program relay will go
into a safety shutdown.
At the completion of the high fire purge period, the program relay signals the modulating damper motor (MDM) to
drive the air damper to its low fire position.
Firing Rate Circuit
•
Damper motor transformer (DMT)
•
Modulating damper motor (MDM)
•
Manual-automatic switch (MAS)
•
Manual flame control (MFC)
•
Modulating control (MC)
High Fire Proving Circuit
•
High fire switch (HFS)
Running Interlock and Limit Circuit
•
Low oil pressure switch (LOPS)
•
High oil pressure switch (HOPS)
•
High oil temperature switch (HOTS)
•
Auxiliary low-water cutoff (ALWCO)
Circuit
Components
Summary of Contents for CBLE
Page 14: ...xiv 750 91 revised 2009 Model CB LE Packaged Boiler Manual...
Page 48: ...Burner Operation and Control 2 22 750 91 revised 2009 Model CB LE Packaged Boiler Manual...
Page 64: ...Waterside Care and Requirements 3 16 750 91 revised 2009 Model CB LE Packaged Boiler Manual...
Page 72: ...Sequence of Operation 4 8 750 91 revised 2009 Model CB LE Packaged Boiler Manual...
Page 158: ...Inspection and Maintenance 8 38 750 91 revised 2009 Model CB LE Packaged Boiler Manual...
Page 166: ...Parts 9 8 750 91 revised 2009 Model CB LE Packaged Boiler Manual Control Panel...
Page 168: ...Parts 9 10 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 7 Front Head Electrical...
Page 170: ...Parts 9 12 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 9 Front Head Insulation...
Page 174: ...Parts 9 16 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 12 Light Oil Air Piping...
Page 176: ...Parts 9 18 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 13 Heavy Oil Air Piping...
Page 182: ...Parts 9 24 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 16 IFGR Impeller...
Page 184: ...Parts 9 26 750 91 revised 2009 Model CB LE Packaged Boiler Manual 9 2 18 Temperature Controls...
Page 186: ...Parts 9 28 750 91 revised 2009 Model CB LE Packaged Boiler Manual W C Main Aux...
Page 193: ......
Page 194: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...