SERVICE MANUAL
–
Post eVolve Smart
9 - OPTIONAL DEVICES
CIRCONTROL, S.A.
–
Innovació, 3
–
08232
–
Viladecavalls (Barcelona)
Tel.: +34 937 362 940
–
Fax: +34 937 362 941
53
Web: www.circontrol.com
–
E-mail:
9.5.1.1
TECHNICAL CHARACTERISTICS
A table of technical specifications of the RCD Type A is shown below:
9.5.1.2
RECLOSURE ATTEMPTS
The RCD with self-reclosing system attempts several times to reclose itself. In the table
below it is specified the timings of the attempts after a residual current detection.
RECLOSURES
1
2
3
Delay
Restart
Delay
Restart
Delay
Restart
<3 sec.
10 sec.
20 sec.
20 sec.
180 sec.
60 sec.
9.5.1.3
RESTART IN CASE OF BLOCKING
I
n case of blocking of the unit, the re-start sequence is:
1
Put the mode selector switch in Manual Mode (OFF).
2
Lift the RCD cover
3
Put the RCD contact in mode ON.
4
Close the RCD cover.
5
Put the mode selector switch in Manual mode (ON).
Note: The switch has an M2 hole where you can attach a seal or a padlock to block the
access to the RCD and any other attempts at manual reclosing.
RCD TYPE A SELF-RECLOSING
Residual
current
device
Type
A
Sensitivity
30 mA
Nominal current
40A
Num. poles
4
Reclosing
system
Number of reclosers
3
Time between reclosers
3, 20, 180 s
Properties
Operating temperature
-
25…+55 ºC
Weight
693g