Technical features
Supply voltage
230/400V Maximum back-up fuse
125 A
Maximum discharge current
(8/20) (L-PE)
–
Imax
40 kA
Short circuit withstand - Isccr
25 kA
Nominal discharge current
(8/20) (L-PE) - In
20 kA
Response time (L-PE)
–
tA (L-PE)
25 ns
Voltage protection level (L-
PE) at In
–
Up (L-PE)
1,3 kV
Remote indication
Yes
9.6.2
FUSE AS A SPAREPART
The fuses that are in the surge protection device can be replaced as a cartridge.
Fuse properties:
-
Replaceable module
-
Class 3
-
Ph
-
Rated current: 40 A (8/20)
-
Rated voltage: 230 V
9.6.3
WIRING CONNECTION
The surge protections shall be wired in parallel to the main circuit in order to discharge
the induced voltage surge.
Following image shows a
detailed schematic of the connections. Please, refer to “
” section for more details