SERVICE MANUAL
–
Post eVolve Smart
9 - OPTIONAL DEVICES
CIRCONTROL, S.A.
–
Innovació, 3
–
08232
–
Viladecavalls (Barcelona)
Tel.: +34 937 362 940
–
Fax: +34 937 362 941
54
Web: www.circontrol.com
–
E-mail:
9.5.1.4
WIRING CONNECTION
Following image shows a detailed schematic of the connections. Please, refer
to “
” section for more details
.
N
POWER SUPPLY
P3
P2
P1
N
P3
P2
P1
Q04.1 (MCB OF PLUG A/B)
9.5.2
TYPE B
–
PHASE I
The RCD type B self-reclosing is composed by an MCB self-reclosing as a mechanical
disconnector and an earth leakage relay as an RCD.
Earth leakage relay
MCB self-reclosing
The tables of technical specifications of the MCB and the Earth Leakage Relay are
shown below:
MCB SELF-RECLOSING
MCB
Max Current
40 A
Nominal cut-off power
(IEC 947-2)
6 kA, in accordance with EN 60898
10 kA, in accordance with EN 60947-2
Characteristic curve
C
Rated working voltage
240 / 415 Vac
Operating temperature
25 ºC...+55 °C
Working frequency range
50 ... 60 Hz
MP motor
Rated voltage
230 Vac ± 30%
Closure time
< 1,000 ms
Opening time
< 10 ms
Reclosing
system
Number of reclosers
3
Time between reclosers
180 s
Reset time reclosers counter
30 m