Section 1: Introduction
CP2000-SB User Manual
2-15
020-100162-06 Rev. 1 (03-2014)
Special Adjustments for Some AC Supplies
AC levels can vary depending on region. Check the following when installing.
NOTES:
1)
Requires voltmeter for up to 400 VAC.
2)
Consult the Interconnect Drawing in pedestal.
3)
Disconnect from AC power before moving the jumpers.
JUMPER FROM IGNITER TERMINAL 2:
As set from the factory, the igniter jumper
located on terminal
2
connects to
T2
. This
configuration is used when 207-265 VAC
are present (as it is for most countries). If
you find your incoming AC is below 207
VAC, connect terminal
2
jumper to
T1
instead.
• If AC between terminals
2
and
3
is
207-265, connect terminal
2
to
T2
(factory default).
• If AC between terminals
2
and
3
is
180-207, connect terminal
2
to
T1
.
See
Figure 2-21
.
BALLAST 115 VAC TAPS:
Ensure your nominal line between the
terminals labeled
115V
and
COMMON
(or
0V
) is within 10% of 115 VAC. See
Figure 2-22
.
• If your measurement at the 115V ter-
minal is
126.5V or more
, move the 115V wires to the tap labeled
–10%.
• If your measurement at the 115V terminal is
103.5V or less
, move the 115V wires to the tap labeled
+10%.
Figure 2-21 Check Voltage and Position Jumper
Figure 2-22 Check Voltage Between 115V and Common (“0V”)
Summary of Contents for CP2000-SB
Page 1: ...CP2000 SB U S E R M A N U A L 020 100162 06 ...
Page 9: ......
Page 15: ...1 6 CP2000 SB User Manual 020 100162 06 Rev 1 03 2014 Section 1 Introduction ...
Page 155: ...8 8 CP2000 SB User Manual 020 100162 06 Rev 1 03 2014 Section 1 Introduction ...
Page 157: ...8 10 CP2000 SB User Manual 020 100162 06 Rev 1 03 2014 Section 1 Introduction ...
Page 173: ...A 16 CP2000 SB User Manual 020 100162 06 Rev 1 03 2014 Section 1 Introduction ...
Page 197: ...B 24 CP2000 SB User Manual 020 100162 06 Rev 1 03 2014 Section 1 Introduction ...