Page 28 of 40 IRIS Connect Series Engineering Manual Version 1.8
CID (Contact ID)
Selecting CID for the inputs means that the inputs will send a specific
Ademco® alarm protocol messages which will include an event code,
zone and group number, on the event and restore for that input. The
following options available are shown below:
SMS
One input can be setup to be SMS by ticking the ‘Set as SMS’ and this
will allow setup of the SMS option as shown above.
Inverse Polarity
The function of the inputs ‘Event’ and ‘Restore’ can be inverted to be
the opposite way round by ticking the ‘Inverse’ tick box. This will mean
that the ‘Event’ is now the closed circuit and the ‘Restore’ event is open
circuit.
Enable
Enable/disable each pin input with the ‘Enable’ tick box.
Monitor Cable
There is also the option to monitor the input for tamper which is
detailed in
Section 7.7 “Pin Inputs”
.
Event
Enter the Event code (3 digits 0-9) for this input for example: 110 = Fire.
To determine which event code is to be used please refer to the Digital Communication Standard -
Ademco® Contact ID Protocol - for Alarm System Communications SIA DC-05-1999.09
Zone
Zone number (Event reports) or User # (Open / Close reports) (3 digits 0-9).
Use 000 to indicate that no specific zone or user information applies.
Group
Group or Partition number (2 digits 0-9).
Use 00 to indicate that no specific group or partition information applies.
Default CID Set/Restore event codes for Pin inputs:
Pin
Number
Contact ID
event code
Zone
number
Group
number
Contact ID event description
1
110
001
00
Fire alarm zone 1
2
120
002
00
Panic alarm zone 2