Page 16 of 40 IRIS Connect Series Engineering Manual Version 1.8
Configuration from Texecom Premier panels via Serial TTL
The IRIS range has been fully integrated into the Texecom Premier Alarm panel range and most configurations can
be configured from the panel keypad.
Connect the IRIS Connect dialler via the TTL header to the Texecom Com 1 header as indicated in
Section 7.4
“Connection”
ensuring that the ‘Serial Selection Header’ is selected for ‘TTL’, then power up the Texecom panel, if
not already powered up.
Below is a detailed description of the configuration setting for the latest Texecom Premier Elite range. If you have
different version of the Texecom Premier range or want to perform upload/download connection via Wintex then
please refer to the IRIS Texecom Premier Installation manual or IRIS Remote Service App Client User Guide for
Texecom range from
http://www.chironsc.com/downloads_security.html
Please use the Texecom keypad or Wintex software to configure the following configuration within the Texecom
alarm panel, please refer to the Texecom Installation guide for further details:
Texecom Premier Elite Series (12, 24, 48, 88, 168, 640)
7 = UDL/DIGI Options
3 = Program Digi
Arc 1 Protocol
- Set to the alarm format requested by the monitoring centre or customer
i.e. Fast Format, Contact ID, or SIA level 2/3.
Primary No
- Set this to the IP address of the monitoring centre in a 12 digit format
i.e. 80.176.196.135 = 080176196135.
Secondary No
- Leave blank as the IRIS System will receive the secondary number from
the monitoring centre IRIS Secure Apps system.
Account Number
- Enter in the account number allocated from the monitoring centre.
Dialler Attempts
- Leave as the default 3.
Report options
- The reporting options will change depending on the alarm format
selected, please set up the various reporting option for the alarm event you
wish to send to the monitoring centre.
Config
- Enable the Connect via IP (Key press 7).
4 = Digi Options
- Enable the Digi (key press 1) should now see E on keypad option screen.
5 = UDL Options
4 = UDL Password
- Must match the UDL password setup within Wintex.
6 = Ring Count
- Set to 1 for use with the IRIS Remote Service App.
7 = Setup Modules
2 = Setup IP Data
1 = ComIP Address
- Leave blank.
2 = ComIP Port
- Program the Port number for Wintex connection normally 10001.
3 = ComIP Gateway
- Leave blank.
4 = ComIP Netmask
-
Leave as default.
5 = Polling/SMG IP
-
Set this to the IP address of the monitoring centre in a 12 digit format
i.e. 80.176.196.135 = 080176196135.
3 = Setup GPRS Data
0 = Access Pnt Name
- Enter the GPRS/3G access point name for the SIM card you are installing.
1 = User Name
- Enter the user name for the SIM card if assigned.
2 = Password
- Enter the password for the SIM card if assigned.
8 = Com Port Setup
2 = Com Port 1
- Set to IRIS IP Module.
The alarm signals commissioning can now be performed and sign off required by the monitoring centre (ARC).