Installation Guide for FibeAir IP-20C-HP
Page 28 of 204
Ceragon Proprietary and Confidential
2.6
Power Specifications
2.6.1
Electrical Requirements
•
-48V DC Nominal
•
Maximum current rating 4A
•
Maximum Cable length 300 meter
2.6.2
Power Connection Options
Power Source
and Range
Data Connection
Type
Connection
Length
DC Cable Type / Gage
Ext DC
-(40.5 ÷ 60)VDC
Optical
≤ 328ft
14AWG
Optical
328ft ÷ 984ft
9AWG
Electrical
≤ 328ft
14AWG
Note:
The 9AWG cable does not fit the IP-20C-
HP’s DC connector so when
using a 9AWG cable, a short adaptor cable from 9AWG to 14AWG
must be used.
2.6.3
Important Notes!
•
The unit must only be installed by service personnel.
•
The unit must have a permanent connection to protective grounding.
•
Data port 2, Data port 3, the Management port, and the TNC connector do not provide
protection from over-voltages on telecommunication networks for host equipment users.
•
The RSL interface connector is intended for technician use only.
•
The disconnect device (circuit breaker) in the building installation:
◦
Shall be readily accessible and incorporated external to the equipment.
◦
The maximum rating of the overcurrent protection shall be up to 6 Amp.
2.7
Environmental Specifications
Operating: ETSI EN 300 019-1-4 Class 4.1
Temperature range for continuous operating temperature with high reliability:
-33°C (-27°F) to +55°C (131°F)
Temperature range for exceptional temperatures; tested successfully, with limited
margins:
-45°C (-49°F) to +60°C (140°F)
Humidity: 5%RH to 100%RH
IEC529 IP66
Storage: ETSI EN 300 019-1-1 Class 1.2
Transportation: ETSI EN 300 019-1-2 Class 2.3