background image

66

might be installed with the hydronic package of the 30RAP
unit is shown on pages 41-43.
  It is recommended that isolation (shutoff) valves be placed
exterior to the unit to allow removal and service of the
entire pump assembly, if necessary. Also, if the unit is iso-
lated with valves, a properly sized pressure relief valve
should be installed in the piping between the unit and the
valves, following all applicable state and local codes.

Water system cleaning

Proper water system cleaning is of vital importance. Exces-
sive particulates in the water system can cause excessive
pump seal wear, reduce or stop flow, and cause damage of
other components. Water quality should be maintained
within the limits indicated in the Water Quality Characteris-
tics and Limitations table.

1. Install a temporary bypass around the chiller to avoid

circulating dirty water and particulates into the pump
package and chiller during the flush. Use a temporary
circulating pump during the cleaning process. Also,
be sure that there is capability to fully drain the sys-
tem after cleaning.

2. Be sure to use a cleaning agent that is compatible

with all system materials. Be especially careful if the
system contains any galvanized or aluminum compo-
nents. Both detergent-dispersant and alkaline-disper-
sant cleaning agents are available.

3. It is a good idea to fill the system through a water

meter. This provides a reference point for the future
for loop volume readings, but it also establishes the
correct quantity of cleaner needed in order to get the
required concentration.

4. Use a feeder/transfer pump to mix the solution and

fill the system. Circulate the cleaning system for the
length of time recommended by the cleaning agent
manufacturer.
a. After cleaning, drain the cleaning fluid and flush

the system with fresh water.

b. A slight amount of cleaning residue in the system

can help keep the desired, slightly alkaline, water
pH of 8 to 9. Avoid a pH greater than 10, since
this will adversely affect pump seal components.

c. A side stream filter is recommended during the

cleaning process. Filter side flow rate should be
enough to filter the entire water volume every 3 to
4 hours. Change filters as often as necessary dur-
ing the cleaning process.

d. Remove temporary bypass when cleaning is

complete.

  A strainer with a blow-down valve is standard on all
30RAP units, both with and without hydronic packages.
The blow-down valve allows removal of particulates caught
in the strainer without complete removal of the screen. A
female NPT connection is provided on the valve, allowing
hose connection for drainage outside the unit.
  The 

Comfort

Link™ controls provided have a built-in fea-

ture to remind building owners or operators to clean the
strainer by discharging the blow-down valve at a pre-set
time interval. Properly installed and cleaned systems will

rarely need the strainer cleaned after the initial fill. This
time interval is user-configurable.

WATER QUALITY CHARACTERISTICS

AND LIMITATIONS

 *Sulfides in the water quickly oxidize when exposed to air, requiring that no

agitation occur as the sample is taken. Unless tested immediately at the
site, the sample will require stabilization with a few drops of one Molar
zinc acetate solution, allowing accurate sulfide determination up to 24
hours after sampling. A low pH and high alkalinity cause system prob-
lems, even when both values are within the ranges shown. The term pH
refers to the acidity, basicity, or neutrality of the water supply. Below 7.0,
the water is considered to be acidic. Above 7.0, water is considered to be
basic. Neutral water contains a pH of 7.0.

†Dissolved carbon dioxide can either be calculated from the pH and total

alkalinity values, shown below, or measured on the site using a test kit.
Dissolved Carbon Dioxide, PPM = TA x 2

[(6.3-pH)/0.3]

 where TA = Total Alka-

linity, PPM as CaCO

3

.

Condenser coil protection (

Enviro-Shield

™)

Refer to the environmental selection guides for more infor-
mation. If the standard Novation

®

 (microchannel) coil does

not meet the corrosion requirements for a given applica-
tion, an e-coated Novation coil option is available. For spe-
cific geographical recommendations, please refer to the
NACO Packaged Chiller Builder program.

E-coated Novation

®

 coils 

have an extremely flexible

and durable epoxy coating uniformly applied to all coil sur-
faces. Unlike brittle phenolic dip and bake coatings, e-coat
provides superior protection with unmatched flexibility,
edge coverage, metal adhesion, thermal performance and
most importantly, corrosion resistance. E-coated coils
provide this protection since all coil surfaces are complete-
ly encapsulated from environmental contamination.

Electrical/utility interests

Energy management —

 Use of energy management

practices can significantly reduce operating costs, espe-
cially during off-peak modes of operation. Demand limiting
and temperature reset are 2 techniques for accomplishing
efficient energy management. See Demand Limiting (also
called load shedding) section on this page for further
details.

Demand limiting (load shedding) — 

When a utility’s

demand for electricity exceeds a certain level, loads are
shed to keep electricity demand below a prescribed maxi-
mum level. Typically, this happens on hot days when air
conditioning is most needed. The energy management
module (EMM) can be added to accomplish this reduction.

 WATER CHARACTERISTIC

QUALITY LIMITATION

Alkalinity (HCO

3

-

)

70 – 300 ppm

Sulfate (SO

4

2-

)

Less than 70 ppm

HCO

3

-

/SO

4

2-

Greater than 1.0

Electrical Conductivity

10 – 500



S/cm

pH

7.5 – 9.0

Ammonium (NH

3

)

Less than 2 ppm

Chorides (Cl

-

)

Less than 300 ppm

Free chlorine (Cl

2

)

Less than 1 ppm

Hydrogen Sulfide (H

2

S)*

Less than 0.05 ppm

Free (aggressive) Carbon
Dioxide (CO

2

)†

Less than 5 ppm

Total Hardness (dH)

4.0 – 8.5

Nitrate (NO

3

)

Less than 100 ppm

Iron (Fe)

Less than 0.2 ppm

Aluminum (Al)

Less than 0.2 ppm

Manganese (Mn)

Less than 0.1 ppm

Application data (cont)

Summary of Contents for Aquasnap 30RAP010

Page 1: ...arrier s AquaSnap chillers feature a compact all in one package design that installs quickly and easily on the ground or the rooftop The optional pump and hydronic components are already built in this...

Page 2: ...it is an entire chilled water system including Single dual pumps up to 15 hp and 160 ft head Regular strainer Cleanout strainer Flow regulator Freeze protection to 20 F 29 C with freeze protection opt...

Page 3: ...equested data the E Cat program output will ad vise the appropriate coil to be used Other factors described in Selection Guide Environmental Corrosion Pro tection Novation Heat Exchanger with Microcha...

Page 4: ...Gas Bypass Std Interrupt Suction Service Valves N Low Ambient Digital Comp Std Interrupt Suction Service Valves P Low Ambient Std Comp High Interrupt Suction Service Valves Q Low Ambient Hot Gas Bypas...

Page 5: ...3 24 5 2 8 27 4 10 3 3 0 15 3 4 5 56 3 3 6 17 8 53 1 030 27 6 97 1 30 9 2 7 33 6 9 9 2 9 14 8 4 3 66 3 4 2 20 9 62 3 035 34 4 121 0 35 9 3 8 39 7 10 4 3 0 14 9 4 4 82 5 5 2 13 2 39 4 040 38 9 136 8 42...

Page 6: ...05 565 565 565 565 565 565 565 450 450 450 Maximum Water Side Pressure Without Pump s psig 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 Maximum Water Side Pressure With Pump s psig 150...

Page 7: ...ithout Pump s kPa 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 Maximum Water Side Pressure With Pump s kPa 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 103...

Page 8: ...93 1171 050 756 873 524 453 2606 050 343 396 238 206 1182 055 768 910 561 474 2713 055 349 413 254 215 1231 060 771 910 562 476 2719 060 350 413 255 216 1233 070 1036 1032 871 874 3812 070 470 468 395...

Page 9: ...ry installed non fused disconnect capability for power and control located at the unit This is not available on dual point power Energy management module EMM provides energy management capabilities to...

Page 10: ...vigator module ideally suited for outdoor applications Magnets located on the back of the module allow attachment of any sheet metal component for hands free operation Remote enhanced display accessor...

Page 11: ...VIDED FOR LOCATING FIELD POWER WIRING ACTUAL HOLE REQUIRED DEPENDS ON FIELD WIRE SIZING 3 0 437 11 10 HOLE USED FOR MOUNTING UNIT 4 UNIT MUST HAVE CLEARANCES AS FOLLOWS TOP DO NOT RESTRICT COIL SIDE 4...

Page 12: ...AVE CLEARANCES AS FOLLOWS TOP DO NOT RESTRICT COIL SIDE 42 1067 FROM SOLID SURFACE PANEL SIDE 48 1219 PER NEC 5 SEE TABLE COLUMN H DIMENSION FOR STANDARD FAN OR VALUE SOUND FAN OPTION 6 CARRIER DOES N...

Page 13: ...W FRONT VIEW CIRCUIT B COMPRESSOR ACCESS TOP VIEW RIGHT VIEW COIL AREA SERVICE CLEARANCE BORDER NOT TO SCALE CG NOTES 1 DO NOT CAP OR OTHERWISE OBSTRUCT THE LIQUID LINE TEMPERATURE RELIEF 2 7 8 22 4 P...

Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...

Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...

Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...

Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...

Page 18: ...ump Curve Option Code Rpm Impeller Dia in Pump Curve non VFD VFD non VFD VFD 010 030 1 5 2 N A 3500 4 25 I 9 N A 3500 4 25 I 3 3 N A 3500 4 75 I B N A 3500 4 75 I 3 high head 4 N A 3500 5 00 I C N A 3...

Page 19: ...010 4 30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5122a 50 7 8 9 10 11 12 40 30 ROP 20 R PRESSURE DR 10 WATER 0 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 2...

Page 20: ...0 HEAT EXCHANGER PRESSURE DROP 30RAP070 090 ENGLISH a30 5350 150 1 6 5 4 3 2 125 100 DROP Kpa 75 ER PRESSURE D 25 50 WATE 0 25 0 1 2 3 4 5 6 7 8 9 10 LITERS SECOND LEGEND 1 30RAP010 4 30RAP020 2 30RAP...

Page 21: ...OND LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 HEAT EXCHANGER PRESSURE DROP 30RAP035 060 SI a30 5125a 40 60 80 100 120 140 160 0 20 40 0 5 10 15 20 25 LITERS SECOND WA...

Page 22: ...30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5126a 50 7 8 9 10 11 12 40 45 30 35 DROP 20 25 TER PRESSURE D 10 15 WAT 0 5 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 1...

Page 23: ...C PACKAGE 30RAP070 090 ENGLISH a30 5356 LEGEND 1 30RAP070 2 30RAP080 3 30RAP090 150 1 2 3 4 5 6 125 100 DROP Kpa 75 ER PRESSURE D 50 WATE 0 25 0 0 1 2 3 4 5 6 7 8 9 10 LITERS SECOND UNIT PRESSURE DROP...

Page 24: ...P035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5129a UNIT PRESSURE DROP NO HYDRONIC PACKAGE 30RAP035 060 SI 50 100 150 200 250 0 50 0 5 10 15 20 25 LITERS SECOND WATER PRESSURE DRO...

Page 25: ...5130a UNIT PRESSURE DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP010 030 ENGLISH 200 160 180 7 9 10 8 120 140 OP 11 12 100 120 R PRESSURE DR 60 80 WATER 20 40 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130...

Page 26: ...ESSURE DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP070 090 ENGLISH a30 5352 300 6 5 4 3 2 1 250 200 OP Kpa 150 PRESSURE DRO 100 WATER 50 0 0 1 2 3 4 5 6 7 8 9 10 11 LITERS SECOND UNIT PRESSURE DROP SINGLE...

Page 27: ...DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP035 060 SI LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5133a 50 100 150 200 250 300 0 50 0 5 10 15 20 25 1 2 3 LITERS SECOND...

Page 28: ...010 4 30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5134a 225 175 200 7 9 10 8 150 ROP 11 12 100 125 R PRESSURE DR 75 WATER 25 50 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Page 29: ...PACKAGE 30RAP070 090 ENGLISH a30 5354 LEGEND 1 30RAP070 2 30RAP080 3 30RAP090 300 6 5 4 3 2 1 250 200 OP Kpa 150 PRESSURE DRO 100 WATER P 50 0 0 1 2 3 4 5 6 7 8 9 10 11 LITERS SECOND UNIT PRESSURE DR...

Page 30: ...IT PRESSURE DROP DUAL PUMP HYDRONIC PACKAGE 30RAP035 060 SI LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5137a 100 150 200 250 300 0 50 0 5 10 15 20 25 LITERS SECOND...

Page 31: ...57 usgpm lps 0 0 0 6 1 20 12 2 40 18 3 60 24 4 80 30 5 100 HEAD m ft FLOW 3500 RPM N P S H r 4 25 in 4 50 in 4 75 in 5 00 in 55 55 53 53 51 51 48 48 43 36 NPSHr 0 75 hp 1 hp 1 5 hp 2 hp 3 hp 5 25 in 4...

Page 32: ...1 47 47 41 41 35 35 27 NPSHr 2 hp 3 hp 5 hp 7 5 hp 10 hp 7 00 in 5 00 in 55 PUMP CURVE II FOR HYDRONIC PACKAGE SINGLE PUMP 5 0 Hp DUAL PUMP 5 0 Hp 30RAP010 030 UNITS LEGEND NOTE Refer to the Pump Impe...

Page 33: ...3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 for proper unit size matching as well as the determination of the impeller diameter NPSHr...

Page 34: ...9 49 42 33 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 20 hp 7 00 in 5 00 in 61 PUMP CURVE IV FOR HYDRONIC PACKAGE SINGLE PUMP 7 5 Hp DUAL PUMP 7 5 Hp SINGLE PUMP 10 0 Hp DUAL PUMP 10 0 Hp LEGEND NOTE Refer to...

Page 35: ...4 00 in usgpm FLOW 3500 RPM 5 hp 1 5 hp 2 hp PUMP CURVE V FOR HYDRONIC PACKAGE SINGLE PUMP 3 Hp SINGLE PUMP 5 Hp UNIT SIZES 070 090 LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 for pr...

Page 36: ...9 58 49 64 69 71 72 usgpm FLOW 3500 RPM 64 69 71 20 hp 15 hp 6 50 in 5 75 in 5 38 in 5 00 in 10 hp 7 5 hp 5 hp 3 hp 58 N P S H r 6 13 in LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 f...

Page 37: ...ermination of the impeller diameter NPSHr Net Pump Suction Head Required 0 0 00 80 5 05 160 10 09 240 15 14 320 20 19 400 25 24 gpm l s us 0 0 0 3 7 12 7 3 24 11 0 36 14 6 48 18 3 60 Head Pressure m f...

Page 38: ...4 90 36 6 120 45 7 150 Head Pressure m ft of fluid Flow Rate 3500 RPM N P S H r 77 77 74 74 70 70 62 62 52 52 39 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 20 hp 6 19 in 6 10 in 5 40 in 77 a30 4393 LEGEND NOT...

Page 39: ...5 90 in 69 69 65 65 60 60 52 52 42 31 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 5 25 in PUMP CURVE IX FOR HYDRONIC PACKAGE DUAL PUMP 7 5 Hp DUAL PUMP 10 Hp a30 4392 LEGEND NOTE Refer to t...

Page 40: ...SSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RAP035 060 30RAP010 030 100 0 10 0 1 0 0 1 10 100 1000 a30 4882 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP kPa 30RAP035 060 30RAP01...

Page 41: ...g must comply with applicable local and national codes 4 All piping must follow standard piping techniques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refri...

Page 42: ...ring must comply with applicable local and national codes 4 All piping must follow standard piping techniques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Re...

Page 43: ...30RAP UNITS WITHOUT HYDRONIC PACKAGE SIZE 070 090 SHOWN LEGEND Airflow Through Condenser Power Wiring Chilled Water Piping NOTES 1 Chiller must be installed level to within 1 8 in per foot 10 4 mm per...

Page 44: ...ion Tank sizes 010 060 only 3 Pump 4 Electric Heater 5 Air Vent Connection Port 6 Pressure Temperature Access Port 7 Heat Exchanger 8 Flow Switch 9 Balance Valve Drain Plug 10 Pressure Relief 11 Isola...

Page 45: ...414 506 1 66 3 90 211 7 80 67 1 90 212 5 80 575 60 518 633 1 58 1 80 160 5 70 58 5 80 160 9 70 035 208 230 60 187 253 1 165 4 200 359 6 175 167 2 200 361 4 200 380 60 342 418 1 103 5 125 218 9 110 10...

Page 46: ...50 438 6 225 181 4 225 451 6 200 380 3 60 342 418 110 8 125 216 2 125 110 5 125 264 0 125 460 3 60 414 506 92 5 110 213 6 100 87 4 110 232 8 100 575 3 60 518 632 79 1 90 163 2 90 77 0 100 179 4 90 090...

Page 47: ...80 181 0 70 61 5 80 182 6 70 63 6 80 184 7 70 575 60 51 2 70 135 3 60 52 6 70 136 7 60 54 2 70 138 3 60 030 208 230 60 141 9 175 412 1 175 145 5 200 415 7 175 150 2 200 420 4 175 380 60 86 7 110 240 2...

Page 48: ...487 2 250 380 60 130 0 150 238 6 150 460 60 106 6 125 232 2 125 575 60 88 4 100 177 7 100 050 208 230 60 254 5 300 490 4 300 261 0 300 496 9 300 380 60 136 4 150 241 8 150 140 0 150 245 4 150 460 60 1...

Page 49: ...IZE 7 5 hp PUMP SIZE 7 5 hp CIRCUIT 1 CIRCUIT 2 MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE 070 208 230 3 60 155 6 200 425 8 175 207 1 250 477 3 225 380 3 60 96 0 125 249 5 110 124 5 150 278 0 150 460...

Page 50: ...3 80 183 4 70 64 4 80 185 5 80 575 60 51 6 70 135 7 60 53 0 70 137 1 60 54 6 70 138 7 60 030 208 230 60 143 1 175 413 3 175 146 7 200 416 9 175 151 4 200 421 6 175 380 60 86 7 110 240 2 100 88 7 110...

Page 51: ...300 489 0 300 380 60 130 0 150 238 6 150 460 60 107 8 125 233 4 125 575 60 89 0 100 178 3 100 050 208 230 60 256 3 300 492 2 300 262 8 300 498 7 300 380 60 136 4 150 241 8 150 140 0 150 245 4 150 460...

Page 52: ...IZE 7 5 hp CIRCUIT 1 CIRCUIT 2 MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE 070 208 230 3 60 158 6 200 428 8 175 207 1 250 477 3 225 380 3 60 96 0 125 249 5 110 124 5 150 278 0 150 460 3 60 77 0 100 22...

Page 53: ...60 60 3 2 9 575 60 3 2 4 040 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3 2 4 045 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3 2 4 050 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3...

Page 54: ...operable as long as the disconnect is on even if any safety device is open and the unit ON OFF switch is in the OFF position UNIT 30RAP UNIT VOLTAGE V Hz 3 Ph STANDARD CONDENSER FANS Quantity FLA eac...

Page 55: ...il MCA 200 to 600 Amps 3 0 AWG to 500 kcmil AWG American Wire Gage MCA Minimum Circuit Amps MOCP VALUE UNIT INCOMING POWER OPTION Standard Terminal Block Option High SCCR Terminal Block Option Standar...

Page 56: ...0 14 3 80 13 4 80 040 2 208 230 60 35 8 239 48 1 245 380 60 23 7 145 23 7 145 460 60 17 9 125 18 6 125 575 60 14 3 80 14 7 100 045 2 208 230 60 48 1 245 51 3 300 380 60 23 7 145 23 7 145 460 60 18 6 1...

Page 57: ...Cooler entering fluid return temperature Outside air temperature Compressor suction temperature Two refrigerant pressure transducers are used in each circuit for sensing suction and discharge pressur...

Page 58: ...de on the display Chiller holds in safety mode until reset It then reverts to normal control when unit is reset Low pressure safety Safety cuts out if system pres sure drops below minimum High pressur...

Page 59: ...ups 30RAP chillers with ComfortLink controls are pre configured with a default setting that assumes stand alone operation sup plying 44 F 6 7 C chilled water Configuration settings will be based on a...

Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...

Page 61: ...econd chiller to meet the addi tional load demand It is also recommended that 2 smaller chillers be installed where operation at minimum load is critical The operation of a smaller chiller loaded to a...

Page 62: ...30RAP chiller does not require a medium tem perature brine modification at any temperature within the chiller application range which is as low as 14 F 10 C leaving fluid temperature Strainers A 40 me...

Page 63: ...ng chiller operation the power and speed of the pump are monitored This enables the controller to establish the hydraulic performance and to position the pump s head flow characteristic Although this...

Page 64: ...ed unit capacity decreases and com pressor power increases Use the NACO North American Commercial Operation Packaged Chiller Builder for cor rections to published ratings Cooler and hydronic system fr...

Page 65: ...g refrigerant lines is never permitted Altitude correction factors Correction factors must be applied to standard ratings at altitudes above 2000 ft 610 m Use the NACO Pack aged Chiller Builder to det...

Page 66: ...tems will rarely need the strainer cleaned after the initial fill This time interval is user configurable WATER QUALITY CHARACTERISTICS AND LIMITATIONS Sulfides in the water quickly oxidize when expos...

Page 67: ...riate measures must be taken for freeze protection Air separation For proper system operation it is essential that water loops be installed with proper means to manage air in the system This is typica...

Page 68: ...NE 3 DISTRIBUTION PUMP EXPANSION TANK S AIR ELIMINATOR WITH VENT MAKEUP FILL SYSTEM DUAL CHILLER LVG SENSOR T COLD WATER TYPICAL MULTIPLE CHILLER CONFIGURATION WITH AIR ELIMINATOR AND EXPANSION TANK L...

Page 69: ...shall submit 1 3 octave band data and sound power data as measured according to AHRI 370 as confirmation of unit sound characteristics 3 Air shall be discharged vertically upward 4 Fans shall be prot...

Page 70: ...to ensure equal pump run time h Dual chiller control for parallel chiller appli cations without addition of hardware modules and control panels additional thermistors and wells are required i Timed m...

Page 71: ...for dual point connection on sizes 070 090 2 Unit shall operate on 3 phase power at the volt age shown in the equipment schedule 3 Control points shall be accessed through termi nal block 4 Unit shall...

Page 72: ...n six programmable digital inputs two analog inputs one programma ble analog digital output two volt free contacts f The hydronic unit shall be capable of operat ing in any of the following control mo...

Page 73: ...re stratification g Tank shall have Victaulic connections h Tank shall have vent and drain plugs accessi ble from outside tank enclosure i Internal heaters shall provide freeze protec tion to 20 F 29...

Page 74: ...ion than the standard unit 21 Compressor Suction Service Valves Sizes 070 090 only Shall provide a suction service valve per circuit which is in addition to the standard discharge service valve 22 Dig...

Page 75: ......

Page 76: ...change at any time specifications or designs without notice and without incurring obligations Pg 76 Catalog No 04 52300039 01 Printed in U S A Form 30RAP 7PD Replaces 30RAP 6PD Book 9 Section 9b Carr...

Reviews: