![Carrier Aquasnap 30RAP010 Product Data Download Page 18](http://html1.mh-extra.com/html/carrier/aquasnap-30rap010/aquasnap-30rap010_product-data_2561845018.webp)
18
Carrier’s electronic catalog chiller selection program pro-
vides quick, easy selection of Carrier chillers. The program
considers specific temperature, fluid, flow requirements,
system pressure drop (for proper pump selection, when
required), as well as other factors, such as fouling and alti-
tude correction.
To select a 30RAP chiller, including optional pump
package when required, use the NACO (North American
Commercial Operation) Packaged Chiller Builder Program.
PUMP IMPELLER SIZES
*Option Code refers to the Hydronics Option (position 12) in the model
number. See the 30RAP nomenclature on page 4 for option identifica-
tion.
NOTE: Pump selections are chiller size dependent. For example, option
code 5 on a 30RAP010-030 chiller is not the same as option code 5 on
a 30RAP035-045 chiller.
UNIT
30RAP
PUMP
Hp
SINGLE PUMP
DUAL PUMP
Option
Code*
Rpm
Impeller
Dia. (in.)
Pump
Curve
Option
Code*
Rpm
Impeller
Dia. (in.)
Pump
Curve
non-VFD
VFD
non-VFD
VFD
010-030
1.5
2
N/A
3500
4.25
I
9
N/A
3500
4.25
I
3
3
N/A
3500
4.75
I
B
N/A
3500
4.75
I
3 (high head)
4
N/A
3500
5.00
I
C
N/A
3500
5.00
I
5
5
N/A
3500
5.50
II
D
N/A
3500
5.50
II
035-045
3
3
N/A
3500
4.75
I
B
N/A
3500
4.75
I
3 (high head)
4
N/A
3500
5.25
I
C
N/A
3500
5.25
I
5
5
N/A
3500
4.50
III
D
N/A
3500
4.50
III
5 (high head)
6
N/A
3500
4.88
III
F
N/A
3500
4.88
III
7.5
7
N/A
3500
5.50
IV
G
N/A
3500
5.50
IV
050-060
3 (high head)
4
N/A
3500
5.25
I
C
N/A
3500
5.25
I
5
5
N/A
3500
4.50
III
D
N/A
3500
4.50
III
5 (high head)
6
N/A
3500
4.88
III
F
N/A
3500
4.88
III
7.5
7
N/A
3500
5.50
IV
G
N/A
3500
5.50
IV
10
Z
N/A
3500
6.00
IV
H
N/A
3500
6.00
IV
070
3
1
C
3500
4.00
V
6
J
1750
6.50
VII
5
2
D
3500
4.75
V
7
K
3500
4.50
VIII
7.5
3
F
3500
5.25
VI
8
L
3500
5.25
IX
10
4
G
3500
5.75
VI
9
M
3500
5.90
IX
0
8
0-090
5
2
D
3500
4.75
V
7
K
3500
4.50
VIII
7.5
3
F
3500
5.25
VI
8
L
3500
5.00
VIII
10
4
G
3500
5.75
VI
9
M
3500
5.40
VIII
15
5
H
3500
6.50
VI
B
N
3500
6.10
VIII
Selection procedure
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...
Page 75: ......