10
interrupter) receptacle with independent fuse protection.
Convenience outlet is 115-v female receptacle. This option
is also available as an accessory.
Compressor suction service valve
provides additional
isolation of the compressor from the cooler vessel for ser-
vice. This option is only available on sizes 070-090.
Hydronic pump package
option adds circulating
pumps, complete with controls, contactor, VFD compati-
ble motors, and insulated expansion tank (expansion tank
available on sizes 010-060 only). Available in single or dual
(lead/lag controlled) cooler pump versions, with total
dynamic head external to the chiller from approximately
15 to 160 ft (4.6 to 48.8 m). A VFD option is available on
sizes 070-090.
Hot gas bypass
option allows additional capacity reduc-
tion for unit operation down below the minimum standard
step of capacity. This option is not available on units with
the digital compressor option or on the 30RAP010 and
015 units. This option is also available as an accessory on
all 30RAP units without digital compressors.
Security grilles/hail guards
consist of louvered, sheet
metal panels which securely fasten to the chiller and pro-
vide condenser coil protection against hail and physical
damage. This option is also available as an accessory.
BACnet communication option —
Provides factory
installed communication capability with a BACnet MS/TP
network. Allows integration with i-Vu
®
Open control sys-
tem or a BACnet building automation system.
Field-installed accessories
BACnet translator control
provides an interface be-
tween the unit and a BACnet Local Area Network (LAN,
i.e., MS/TP EIA-485). Field programming is required.
Chillervisor System Manager III multi-unit control
accessory allows sequencing of between two and eight
chillers in parallel. Pump control is also provided.
Energy management module
provides energy manage-
ment capabilities to minimize chiller energy consumption.
Several features are provided with this module including
leaving fluid temperature reset, cooling set point reset or
demand limit control from a 4 to 20 mA signal, 2-point
demand limit control (from 0 to 100%) activated by a
remote contact closure, and discrete input for “Ice Done”
indication for ice storage system interface. The EMM is
also available as an option.
LON (local operating network) translator control
provides an interface between the unit and a local operat-
ing network (i.e., LonWorks* FT-10A ANSI/EIA-709.1).
Field programming is required.
Navigator™ display module
provides a portable, hand
held display module for convenient access to unit status,
operation, configuration and troubleshooting diagnostics
capability. The 4-line, 80-character LCD (liquid crystal
display) display provides clear language information in
English, French, Spanish or Portuguese. The weatherproof
enclosure and industrial grade extension cord make the
Navigator module ideally suited for outdoor applications.
Magnets located on the back of the module allow
attachment of any sheet metal component for hands free
operation.
Remote enhanced display
accessory kit contains a
remotely mounted 40-character per line, 16-line display
panel for unit diagnostics.
Touch Pilot™ display
is a cost-effective, touch-screen,
remote-mount device that can be used in lieu of the remote
enhanced display.
Motormaster
®
V low-ambient control
provides con-
trol of outdoor-fan motor operation to maintain head pres-
sure at low outdoor ambient temperatures down to –20 F
(–29 C). This accessory also requires field-installed wind
baffles. This accessory is also available as a factory-installed
option. This accessory is standard on 30RAP010 and 015
units.
Chilled water storage tank
provides a minimum of
4 gallons per ton loop storage capacity. Includes insulated
steel shell tank, Victaulic pipe connections, electric tank
heaters, electric cables, vent, drain, and enclosure to allow
tank to be installed under the chiller to protect to –20 F
(–29 C). The power supply for the storage tank is obtained
from the chiller, so no separate power source is required
for this accessory. This is available with sizes 010-060
only.
Vibration isolation
consists of field-installed
1
/
4
-in.
(0.64 cm) neoprene isolator pads (24-in. x 3-in.) (61.0 cm
x 7.6 cm) that reduce vibration transmission from the com-
pressor through the floor and into the conditioned space.
Low sound compressor blankets
reduce unit sound
levels by providing an acoustic blanket on each compres-
sor.
Hot gas bypass
accessory allows additional capacity re-
duction for unit operation below the minimum standard
step of capacity. This accessory is not available on units
which have the digital compressor option. This field-in-
stalled accessory is also available as a factory-installed op-
tion, but the factory option is not available with digital com-
pressors or unit sizes of 010 or 015.
Remote cooler kit
provides the additional hardware re-
quired to remotely mount the cooler from the unit. There
are limits to total separation of the unit to the cooler as well
as vertical separation limits, and these are delineated in the
accessory installation instructions. Never bury refrigerant
piping on these or any other applications.
GFI convenience outlet
is a field-installed convenience
outlet that includes a 4-amp GFI (ground fault interrupter)
receptacle with independent fuse protection. The conve-
nience outlet is a 115-v female receptacle. The GFI conve-
nience outlet is also available as a factory-installed option.
Security grilles/hail guards
consist of louvered, sheet
metal panels which securely fasten to the chiller and pro-
vide condenser coil protection against hail and physical
damage. Security grilles/hail guards are also available as a
factory-installed option.
Wind baffles
facilitate operation down to –20 F (–29 C)
when used in conjunction with low ambient temperature
head pressure control.
Options and accessories (cont)
*Registered trademark of Echelon Corporation.
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...
Page 75: ......