52
30RAP ELECTRICAL DATA (cont)
DUAL POINT HYDRONIC PACKAGE WITH OPTIONAL VALUE SOUND FANS
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2
%
; amps 10
%
.
2. All units/modules have dual point primary power connection. (Each unit/module requires its
own power supply.) Main power must be supplied from a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the power
supply disconnect is on, even if any safety device is open.
4. Power draw control circuits include cooler heaters (where used).
3
8
RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 3.0 hp
PUMP SIZE 3.0 hp
CIRCUIT 1
CIRCUIT 2
MCA
MOCP
ICF
REC FUSE
MCA
MOCP
ICF
REC FUSE
070
208/230-3-60
158.6
200
428.8
175
192.2
225
462.4
225
380-3-60
96.0
125
249.5
110
116.4
150
269.9
125
460-3-60
77.0
100
222.4
90
92.3
110
237.7
100
575-3-60
66.3
90
168.7
80
80.9
100
183.3
90
0
8
0
208/230-3-60
—
—
—
—
—
—
—
—
380-3-60
—
—
—
—
—
—
—
—
460-3-60
—
—
—
—
—
—
—
—
575-3-60
—
—
—
—
—
—
—
—
090
208/230-3-60
—
—
—
—
—
—
—
—
380-3-60
—
—
—
—
—
—
—
—
460-3-60
—
—
—
—
—
—
—
—
575-3-60
—
—
—
—
—
—
—
—
3
8
RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 5.0 hp
PUMP SIZE 5.0 hp
CIRCUIT 1
CIRCUIT 2
MCA
MOCP
ICF
REC FUSE
MCA
MOCP
ICF
REC FUSE
070
208/230-3-60
158.6
200
428.8
175
199.1
250
469.3
225
380-3-60
96.0
125
249.5
110
120.2
150
273.7
150
460-3-60
77.0
100
222.4
90
95.4
110
240.8
110
575-3-60
66.3
90
168.7
80
83.4
100
185.8
90
0
8
0
208/230-3-60
206.3
250
442.2
225
199.1
250
469.3
225
380-3-60
110.8
125
216.2
125
120.2
150
273.7
150
460-3-60
94.9
110
216.0
110
95.4
110
240.8
110
575-3-60
80.3
100
164.4
90
83.4
100
185.8
90
090
208/230-3-60
221.0
250
491.2
250
199.1
250
469.3
225
380-3-60
133.9
150
287.4
150
120.2
150
273.7
150
460-3-60
107.2
125
252.6
125
95.4
110
240.8
110
575-3-60
92.6
110
195.0
100
83.4
100
185.8
90
3
8
RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 7.5 hp
PUMP SIZE 7.5 hp
CIRCUIT 1
CIRCUIT 2
MCA
MOCP
ICF
REC FUSE
MCA
MOCP
ICF
REC FUSE
070
208/230-3-60
158.6
200
428.8
175
207.1
250
477.3
225
380-3-60
96.0
125
249.5
110
124.5
150
278.0
150
460-3-60
77.0
100
222.4
90
99.0
125
244.4
110
575-3-60
66.3
90
168.7
80
86.3
110
188.7
100
0
8
0
208/230-3-60
206.3
250
442.2
225
207.1
250
477.3
225
380-3-60
110.8
125
216.2
125
124.5
150
278.0
150
460-3-60
94.9
110
216.0
110
99.0
125
244.4
110
575-3-60
80.3
100
164.4
90
86.3
110
188.7
100
090
208/230-3-60
221.0
250
491.2
250
207.1
250
477.3
225
380-3-60
133.9
150
287.4
150
124.5
150
278.0
150
460-3-60
107.2
125
252.6
125
99.0
125
244.4
110
575-3-60
92.6
110
195.0
100
86.3
110
188.7
100
3
8
RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 10.0 hp
PUMP SIZE 10.0 hp
CIRCUIT 1
CIRCUIT 2
MCA
MOCP
ICF
REC FUSE
MCA
MOCP
ICF
REC FUSE
070
208/230-3-60
158.6
200
428.8
175
215.0
250
485.2
225
380-3-60
96.0
125
249.5
110
128.9
150
282.4
150
460-3-60
77.0
100
222.4
90
102.6
125
248.0
110
575-3-60
66.3
90
168.7
80
89.2
110
191.6
100
0
8
0
208/230-3-60
206.3
250
442.2
225
215.0
250
485.2
225
380-3-60
110.8
125
216.2
125
128.9
150
282.4
150
460-3-60
94.9
110
216.0
110
102.6
125
248.0
110
575-3-60
80.3
100
164.4
90
89.2
110
191.6
100
090
208/230-3-60
221.0
250
491.2
250
215.0
250
485.2
225
380-3-60
133.9
150
287.4
150
128.9
150
282.4
150
460-3-60
107.2
125
252.6
125
102.6
125
248.0
110
575-3-60
92.6
110
195.0
100
89.2
110
191.6
100
3
8
RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 15.0 hp
PUMP SIZE 15.0 hp
CIRCUIT 1
CIRCUIT 2
MCA
MOCP
ICF
REC FUSE
MCA
MOCP
ICF
REC FUSE
070
208/230-3-60
—
—
—
—
—
—
—
—
380-3-60
—
—
—
—
—
—
—
—
460-3-60
—
—
—
—
—
—
—
—
575-3-60
—
—
—
—
—
—
—
—
0
8
0
208/230-3-60
206.3
250
442.2
225
231.2
250
501.4
225
380-3-60
110.8
125
216.2
125
137.7
150
291.2
150
460-3-60
94.9
110
216.0
110
109.9
125
255.3
110
575-3-60
80.3
100
164.4
90
95.0
110
197.4
100
090
208/230-3-60
221.0
250
491.2
250
231.2
250
501.4
225
380-3-60
133.9
150
287.4
150
137.7
150
291.2
150
460-3-60
107.2
125
252.6
125
109.9
125
255.3
110
575-3-60
92.6
110
195.0
100
95.0
110
197.4
100
ICF
—
Instantaneous Current Flow
MCA
—
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
Electrical data (cont)
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...
Page 75: ......