background image

57

Controls

Microprocessor — 

The 

Comfort

Link™ microprocessor

controls overall unit operation. Its central executive routine
controls a number of processes simultaneously. These
include internal timers, reading inputs, analog to digital
conversions, fan control, display control, diagnostic con-
trol, output relay control, demand limit, capacity control,
head pressure control, and temperature reset. Some pro-
cesses are updated almost continuously, others every 2 to
3 seconds, and some every 30 seconds. The microproces-
sor routine is started by switching the Emergency ON-OFF
switch to ON position. Pump control of external pumps
(where so configured) or optional internal pump, will
energize the cooler pump to the internal (or CCN) time
schedule (or input occupied signal from external system).

Where dual pumps are utilized, only one pump will be

used at a time. The control will start the pump with the
least number of operating hours. When the unit receives a
call for cooling (based on a deviation from chilled water set
point), the unit stages up in capacity to maintain the cooler
fluid set point. The first compressor starts 1 to 3 minutes
after the call for cooling. The 

Comfort

Link microproces-

sor controls the capacity of the chiller by cycling compres-
sors at a rate to satisfy actual dynamic load conditions. The
control maintains leaving-fluid temperature set point
shown on the scrolling marquee display board through
intelligent cycling of compressors. Accuracy depends on
loop volume, loop flow rate, load, outdoor-air temperature,
number of stages, and particular stage being cycled off. No
adjustment for cooling range or cooler flow rate is
required, because the control automatically compensates
for cooling range by measuring both return-fluid tempera-
ture and leaving-fluid temperature. This is referred to as
leaving-fluid temperature control with return-fluid tempera-
ture compensation. 

The basic logic for determining when to add or remove a

stage is a time band integration of deviation from set point
plus  rate  of  change  of  leaving-fluid temperature. When
leaving-fluid temperature is close to set point and slowly
moving closer, logic prevents addition of another stage.

If 1° F per minute (0.6° C per minute) pulldown control

has been selected (adjustable setting), no additional steps of
capacity are added as long as difference between leaving-
fluid temperature and set point is greater than 4° F (2.2° C)
and rate of change in leaving-fluid temperature is greater
than the selected pulldown control rate. If it has been less
than 90 seconds since the last capacity change, compres-
sors will continue to run unless a safety device trips. This
prevents rapid cycling and also helps return oil during short
on periods.

Sensors —

 Thermistors are used for temperature-sensing

inputs to microprocessor. Additional thermistor sensors
may be used as remote temperature sensors for optional
LCWT (leaving chilled fluid temperature) reset.
• Cooler leaving chilled fluid temperature
• Cooler entering fluid (return) temperature
• Outside air temperature
• Compressor suction temperature

Two refrigerant pressure transducers are used in each

circuit for sensing suction and discharge pressure. The
microprocessor uses these inputs to control capacity, the
electronic expansion valve, and fan cycling.

• Saturated condensing temperature
• Cooler saturation temperature

Control sequence

Off cycle —

 If ambient temperature is below 36 F (2 C),

cooler heaters (if equipped) are also energized.

Start-up —

 After control circuit switches on, the prestart

process takes place, then microprocessor checks itself,
starts pump (if configured) and waits for temperature to
stabilize. The controlled pulldown feature limits compres-
sor loading on start-up to reduce demand on start-up and
unnecessary compressor usage. The microprocessor limits
supply-fluid temperature decrease (start-up only) to 1° F
(0.6° C) per minute.

Capacity control —

 On first call for cooling, micropro-

cessor starts initial compressor and fan stage on lead
circuit.

As additional cooling is required, additional compressors

are energized.

Speed at which capacity is added or reduced is con-

trolled by temperature deviation from set point and rate of
temperature change of chilled fluid.

The Main Base Board (MBB) responds to temperature of

supply chilled water to cycle the compressor(s) and to con-
trol compressor unloading and loading to match cooling
load requirements.

Hot gas bypass valve is energized by the MBB. Valve

allows hot gas to pass directly into the cooler circuit on the
final step of unloading, maintaining constant suction pres-
sure and permitting the unit to operate at lower loads with
less compressor cycling.

On units equipped with the digital compressor option,

the control will intigrate the modulation of the digital com-
pressor into the capacity routine to match cooling load
requirements. The digital compressor will modulate in 13
steps for sizes 010 and 015, 22 steps (11 per compressor)
for sizes 020-030, 44 steps (11 per compressor) for sizes
035-060, 55 steps for size 070 and 66 steps for sizes 080-
090. 
The digital scroll option provides better capacity control by
incrementally modulating capacity effectively, increasing
the number of compression stages compared to chillers
that are not equipped with this option. The digital scroll
compressor is not a variable speed device, it modulates the
capacity output by allowing the scroll sets to separate dur-
ing operation, alternating between full capacity and zero
capacity.  Utilizing a fixed timeframe ratio,  the percentage
of time that the scroll set is engaged is the percentage
capacity of that compressor.
There are 2 major advantages of this type of capacity con-
trol. First, there is closer capacity control operation with all
the available capacity steps compared to the on/off cycling
control of conventional scrolls. Second, there is much less
wear factor on digital scrolls compared to standard scroll
compressors because the digital scrolls are not subject to as
many of the shutdown/restart cycles as conventional
scrolls. Digital scrolls, rather than shutting off, tend to
remain on as they vary to deliver the correct capacity step.

Summary of Contents for Aquasnap 30RAP010

Page 1: ...arrier s AquaSnap chillers feature a compact all in one package design that installs quickly and easily on the ground or the rooftop The optional pump and hydronic components are already built in this...

Page 2: ...it is an entire chilled water system including Single dual pumps up to 15 hp and 160 ft head Regular strainer Cleanout strainer Flow regulator Freeze protection to 20 F 29 C with freeze protection opt...

Page 3: ...equested data the E Cat program output will ad vise the appropriate coil to be used Other factors described in Selection Guide Environmental Corrosion Pro tection Novation Heat Exchanger with Microcha...

Page 4: ...Gas Bypass Std Interrupt Suction Service Valves N Low Ambient Digital Comp Std Interrupt Suction Service Valves P Low Ambient Std Comp High Interrupt Suction Service Valves Q Low Ambient Hot Gas Bypas...

Page 5: ...3 24 5 2 8 27 4 10 3 3 0 15 3 4 5 56 3 3 6 17 8 53 1 030 27 6 97 1 30 9 2 7 33 6 9 9 2 9 14 8 4 3 66 3 4 2 20 9 62 3 035 34 4 121 0 35 9 3 8 39 7 10 4 3 0 14 9 4 4 82 5 5 2 13 2 39 4 040 38 9 136 8 42...

Page 6: ...05 565 565 565 565 565 565 565 450 450 450 Maximum Water Side Pressure Without Pump s psig 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 Maximum Water Side Pressure With Pump s psig 150...

Page 7: ...ithout Pump s kPa 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 Maximum Water Side Pressure With Pump s kPa 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 103...

Page 8: ...93 1171 050 756 873 524 453 2606 050 343 396 238 206 1182 055 768 910 561 474 2713 055 349 413 254 215 1231 060 771 910 562 476 2719 060 350 413 255 216 1233 070 1036 1032 871 874 3812 070 470 468 395...

Page 9: ...ry installed non fused disconnect capability for power and control located at the unit This is not available on dual point power Energy management module EMM provides energy management capabilities to...

Page 10: ...vigator module ideally suited for outdoor applications Magnets located on the back of the module allow attachment of any sheet metal component for hands free operation Remote enhanced display accessor...

Page 11: ...VIDED FOR LOCATING FIELD POWER WIRING ACTUAL HOLE REQUIRED DEPENDS ON FIELD WIRE SIZING 3 0 437 11 10 HOLE USED FOR MOUNTING UNIT 4 UNIT MUST HAVE CLEARANCES AS FOLLOWS TOP DO NOT RESTRICT COIL SIDE 4...

Page 12: ...AVE CLEARANCES AS FOLLOWS TOP DO NOT RESTRICT COIL SIDE 42 1067 FROM SOLID SURFACE PANEL SIDE 48 1219 PER NEC 5 SEE TABLE COLUMN H DIMENSION FOR STANDARD FAN OR VALUE SOUND FAN OPTION 6 CARRIER DOES N...

Page 13: ...W FRONT VIEW CIRCUIT B COMPRESSOR ACCESS TOP VIEW RIGHT VIEW COIL AREA SERVICE CLEARANCE BORDER NOT TO SCALE CG NOTES 1 DO NOT CAP OR OTHERWISE OBSTRUCT THE LIQUID LINE TEMPERATURE RELIEF 2 7 8 22 4 P...

Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...

Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...

Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...

Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...

Page 18: ...ump Curve Option Code Rpm Impeller Dia in Pump Curve non VFD VFD non VFD VFD 010 030 1 5 2 N A 3500 4 25 I 9 N A 3500 4 25 I 3 3 N A 3500 4 75 I B N A 3500 4 75 I 3 high head 4 N A 3500 5 00 I C N A 3...

Page 19: ...010 4 30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5122a 50 7 8 9 10 11 12 40 30 ROP 20 R PRESSURE DR 10 WATER 0 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 2...

Page 20: ...0 HEAT EXCHANGER PRESSURE DROP 30RAP070 090 ENGLISH a30 5350 150 1 6 5 4 3 2 125 100 DROP Kpa 75 ER PRESSURE D 25 50 WATE 0 25 0 1 2 3 4 5 6 7 8 9 10 LITERS SECOND LEGEND 1 30RAP010 4 30RAP020 2 30RAP...

Page 21: ...OND LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 HEAT EXCHANGER PRESSURE DROP 30RAP035 060 SI a30 5125a 40 60 80 100 120 140 160 0 20 40 0 5 10 15 20 25 LITERS SECOND WA...

Page 22: ...30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5126a 50 7 8 9 10 11 12 40 45 30 35 DROP 20 25 TER PRESSURE D 10 15 WAT 0 5 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 1...

Page 23: ...C PACKAGE 30RAP070 090 ENGLISH a30 5356 LEGEND 1 30RAP070 2 30RAP080 3 30RAP090 150 1 2 3 4 5 6 125 100 DROP Kpa 75 ER PRESSURE D 50 WATE 0 25 0 0 1 2 3 4 5 6 7 8 9 10 LITERS SECOND UNIT PRESSURE DROP...

Page 24: ...P035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5129a UNIT PRESSURE DROP NO HYDRONIC PACKAGE 30RAP035 060 SI 50 100 150 200 250 0 50 0 5 10 15 20 25 LITERS SECOND WATER PRESSURE DRO...

Page 25: ...5130a UNIT PRESSURE DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP010 030 ENGLISH 200 160 180 7 9 10 8 120 140 OP 11 12 100 120 R PRESSURE DR 60 80 WATER 20 40 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130...

Page 26: ...ESSURE DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP070 090 ENGLISH a30 5352 300 6 5 4 3 2 1 250 200 OP Kpa 150 PRESSURE DRO 100 WATER 50 0 0 1 2 3 4 5 6 7 8 9 10 11 LITERS SECOND UNIT PRESSURE DROP SINGLE...

Page 27: ...DROP SINGLE PUMP HYDRONIC PACKAGE 30RAP035 060 SI LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5133a 50 100 150 200 250 300 0 50 0 5 10 15 20 25 1 2 3 LITERS SECOND...

Page 28: ...010 4 30RAP020 2 30RAP015 5 30RAP025 3 30RAP018 6 30RAP030 a30 5134a 225 175 200 7 9 10 8 150 ROP 11 12 100 125 R PRESSURE DR 75 WATER 25 50 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Page 29: ...PACKAGE 30RAP070 090 ENGLISH a30 5354 LEGEND 1 30RAP070 2 30RAP080 3 30RAP090 300 6 5 4 3 2 1 250 200 OP Kpa 150 PRESSURE DRO 100 WATER P 50 0 0 1 2 3 4 5 6 7 8 9 10 11 LITERS SECOND UNIT PRESSURE DR...

Page 30: ...IT PRESSURE DROP DUAL PUMP HYDRONIC PACKAGE 30RAP035 060 SI LEGEND 7 30RAP035 10 30RAP050 8 30RAP040 11 30RAP055 9 30RAP045 12 30RAP060 a30 5137a 100 150 200 250 300 0 50 0 5 10 15 20 25 LITERS SECOND...

Page 31: ...57 usgpm lps 0 0 0 6 1 20 12 2 40 18 3 60 24 4 80 30 5 100 HEAD m ft FLOW 3500 RPM N P S H r 4 25 in 4 50 in 4 75 in 5 00 in 55 55 53 53 51 51 48 48 43 36 NPSHr 0 75 hp 1 hp 1 5 hp 2 hp 3 hp 5 25 in 4...

Page 32: ...1 47 47 41 41 35 35 27 NPSHr 2 hp 3 hp 5 hp 7 5 hp 10 hp 7 00 in 5 00 in 55 PUMP CURVE II FOR HYDRONIC PACKAGE SINGLE PUMP 5 0 Hp DUAL PUMP 5 0 Hp 30RAP010 030 UNITS LEGEND NOTE Refer to the Pump Impe...

Page 33: ...3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 for proper unit size matching as well as the determination of the impeller diameter NPSHr...

Page 34: ...9 49 42 33 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 20 hp 7 00 in 5 00 in 61 PUMP CURVE IV FOR HYDRONIC PACKAGE SINGLE PUMP 7 5 Hp DUAL PUMP 7 5 Hp SINGLE PUMP 10 0 Hp DUAL PUMP 10 0 Hp LEGEND NOTE Refer to...

Page 35: ...4 00 in usgpm FLOW 3500 RPM 5 hp 1 5 hp 2 hp PUMP CURVE V FOR HYDRONIC PACKAGE SINGLE PUMP 3 Hp SINGLE PUMP 5 Hp UNIT SIZES 070 090 LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 for pr...

Page 36: ...9 58 49 64 69 71 72 usgpm FLOW 3500 RPM 64 69 71 20 hp 15 hp 6 50 in 5 75 in 5 38 in 5 00 in 10 hp 7 5 hp 5 hp 3 hp 58 N P S H r 6 13 in LEGEND NOTE Refer to the Pump Impeller Sizes chart on page 18 f...

Page 37: ...ermination of the impeller diameter NPSHr Net Pump Suction Head Required 0 0 00 80 5 05 160 10 09 240 15 14 320 20 19 400 25 24 gpm l s us 0 0 0 3 7 12 7 3 24 11 0 36 14 6 48 18 3 60 Head Pressure m f...

Page 38: ...4 90 36 6 120 45 7 150 Head Pressure m ft of fluid Flow Rate 3500 RPM N P S H r 77 77 74 74 70 70 62 62 52 52 39 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 20 hp 6 19 in 6 10 in 5 40 in 77 a30 4393 LEGEND NOT...

Page 39: ...5 90 in 69 69 65 65 60 60 52 52 42 31 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 5 25 in PUMP CURVE IX FOR HYDRONIC PACKAGE DUAL PUMP 7 5 Hp DUAL PUMP 10 Hp a30 4392 LEGEND NOTE Refer to t...

Page 40: ...SSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RAP035 060 30RAP010 030 100 0 10 0 1 0 0 1 10 100 1000 a30 4882 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP kPa 30RAP035 060 30RAP01...

Page 41: ...g must comply with applicable local and national codes 4 All piping must follow standard piping techniques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refri...

Page 42: ...ring must comply with applicable local and national codes 4 All piping must follow standard piping techniques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Re...

Page 43: ...30RAP UNITS WITHOUT HYDRONIC PACKAGE SIZE 070 090 SHOWN LEGEND Airflow Through Condenser Power Wiring Chilled Water Piping NOTES 1 Chiller must be installed level to within 1 8 in per foot 10 4 mm per...

Page 44: ...ion Tank sizes 010 060 only 3 Pump 4 Electric Heater 5 Air Vent Connection Port 6 Pressure Temperature Access Port 7 Heat Exchanger 8 Flow Switch 9 Balance Valve Drain Plug 10 Pressure Relief 11 Isola...

Page 45: ...414 506 1 66 3 90 211 7 80 67 1 90 212 5 80 575 60 518 633 1 58 1 80 160 5 70 58 5 80 160 9 70 035 208 230 60 187 253 1 165 4 200 359 6 175 167 2 200 361 4 200 380 60 342 418 1 103 5 125 218 9 110 10...

Page 46: ...50 438 6 225 181 4 225 451 6 200 380 3 60 342 418 110 8 125 216 2 125 110 5 125 264 0 125 460 3 60 414 506 92 5 110 213 6 100 87 4 110 232 8 100 575 3 60 518 632 79 1 90 163 2 90 77 0 100 179 4 90 090...

Page 47: ...80 181 0 70 61 5 80 182 6 70 63 6 80 184 7 70 575 60 51 2 70 135 3 60 52 6 70 136 7 60 54 2 70 138 3 60 030 208 230 60 141 9 175 412 1 175 145 5 200 415 7 175 150 2 200 420 4 175 380 60 86 7 110 240 2...

Page 48: ...487 2 250 380 60 130 0 150 238 6 150 460 60 106 6 125 232 2 125 575 60 88 4 100 177 7 100 050 208 230 60 254 5 300 490 4 300 261 0 300 496 9 300 380 60 136 4 150 241 8 150 140 0 150 245 4 150 460 60 1...

Page 49: ...IZE 7 5 hp PUMP SIZE 7 5 hp CIRCUIT 1 CIRCUIT 2 MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE 070 208 230 3 60 155 6 200 425 8 175 207 1 250 477 3 225 380 3 60 96 0 125 249 5 110 124 5 150 278 0 150 460...

Page 50: ...3 80 183 4 70 64 4 80 185 5 80 575 60 51 6 70 135 7 60 53 0 70 137 1 60 54 6 70 138 7 60 030 208 230 60 143 1 175 413 3 175 146 7 200 416 9 175 151 4 200 421 6 175 380 60 86 7 110 240 2 100 88 7 110...

Page 51: ...300 489 0 300 380 60 130 0 150 238 6 150 460 60 107 8 125 233 4 125 575 60 89 0 100 178 3 100 050 208 230 60 256 3 300 492 2 300 262 8 300 498 7 300 380 60 136 4 150 241 8 150 140 0 150 245 4 150 460...

Page 52: ...IZE 7 5 hp CIRCUIT 1 CIRCUIT 2 MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE 070 208 230 3 60 158 6 200 428 8 175 207 1 250 477 3 225 380 3 60 96 0 125 249 5 110 124 5 150 278 0 150 460 3 60 77 0 100 22...

Page 53: ...60 60 3 2 9 575 60 3 2 4 040 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3 2 4 045 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3 2 4 050 208 230 60 3 6 0 380 60 3 3 9 460 60 3 2 9 575 60 3...

Page 54: ...operable as long as the disconnect is on even if any safety device is open and the unit ON OFF switch is in the OFF position UNIT 30RAP UNIT VOLTAGE V Hz 3 Ph STANDARD CONDENSER FANS Quantity FLA eac...

Page 55: ...il MCA 200 to 600 Amps 3 0 AWG to 500 kcmil AWG American Wire Gage MCA Minimum Circuit Amps MOCP VALUE UNIT INCOMING POWER OPTION Standard Terminal Block Option High SCCR Terminal Block Option Standar...

Page 56: ...0 14 3 80 13 4 80 040 2 208 230 60 35 8 239 48 1 245 380 60 23 7 145 23 7 145 460 60 17 9 125 18 6 125 575 60 14 3 80 14 7 100 045 2 208 230 60 48 1 245 51 3 300 380 60 23 7 145 23 7 145 460 60 18 6 1...

Page 57: ...Cooler entering fluid return temperature Outside air temperature Compressor suction temperature Two refrigerant pressure transducers are used in each circuit for sensing suction and discharge pressur...

Page 58: ...de on the display Chiller holds in safety mode until reset It then reverts to normal control when unit is reset Low pressure safety Safety cuts out if system pres sure drops below minimum High pressur...

Page 59: ...ups 30RAP chillers with ComfortLink controls are pre configured with a default setting that assumes stand alone operation sup plying 44 F 6 7 C chilled water Configuration settings will be based on a...

Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...

Page 61: ...econd chiller to meet the addi tional load demand It is also recommended that 2 smaller chillers be installed where operation at minimum load is critical The operation of a smaller chiller loaded to a...

Page 62: ...30RAP chiller does not require a medium tem perature brine modification at any temperature within the chiller application range which is as low as 14 F 10 C leaving fluid temperature Strainers A 40 me...

Page 63: ...ng chiller operation the power and speed of the pump are monitored This enables the controller to establish the hydraulic performance and to position the pump s head flow characteristic Although this...

Page 64: ...ed unit capacity decreases and com pressor power increases Use the NACO North American Commercial Operation Packaged Chiller Builder for cor rections to published ratings Cooler and hydronic system fr...

Page 65: ...g refrigerant lines is never permitted Altitude correction factors Correction factors must be applied to standard ratings at altitudes above 2000 ft 610 m Use the NACO Pack aged Chiller Builder to det...

Page 66: ...tems will rarely need the strainer cleaned after the initial fill This time interval is user configurable WATER QUALITY CHARACTERISTICS AND LIMITATIONS Sulfides in the water quickly oxidize when expos...

Page 67: ...riate measures must be taken for freeze protection Air separation For proper system operation it is essential that water loops be installed with proper means to manage air in the system This is typica...

Page 68: ...NE 3 DISTRIBUTION PUMP EXPANSION TANK S AIR ELIMINATOR WITH VENT MAKEUP FILL SYSTEM DUAL CHILLER LVG SENSOR T COLD WATER TYPICAL MULTIPLE CHILLER CONFIGURATION WITH AIR ELIMINATOR AND EXPANSION TANK L...

Page 69: ...shall submit 1 3 octave band data and sound power data as measured according to AHRI 370 as confirmation of unit sound characteristics 3 Air shall be discharged vertically upward 4 Fans shall be prot...

Page 70: ...to ensure equal pump run time h Dual chiller control for parallel chiller appli cations without addition of hardware modules and control panels additional thermistors and wells are required i Timed m...

Page 71: ...for dual point connection on sizes 070 090 2 Unit shall operate on 3 phase power at the volt age shown in the equipment schedule 3 Control points shall be accessed through termi nal block 4 Unit shall...

Page 72: ...n six programmable digital inputs two analog inputs one programma ble analog digital output two volt free contacts f The hydronic unit shall be capable of operat ing in any of the following control mo...

Page 73: ...re stratification g Tank shall have Victaulic connections h Tank shall have vent and drain plugs accessi ble from outside tank enclosure i Internal heaters shall provide freeze protec tion to 20 F 29...

Page 74: ...ion than the standard unit 21 Compressor Suction Service Valves Sizes 070 090 only Shall provide a suction service valve per circuit which is in addition to the standard discharge service valve 22 Dig...

Page 75: ......

Page 76: ...change at any time specifications or designs without notice and without incurring obligations Pg 76 Catalog No 04 52300039 01 Printed in U S A Form 30RAP 7PD Replaces 30RAP 6PD Book 9 Section 9b Carr...

Reviews: