FAN ELECTRICAL DATA
(Dual Point Standard Low-Sound AeroAcoustic™ Fans)
FAN ELECTRICAL DATA
(Dual Point Optional Value Sound Fans)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed minimum and max-
imum limits. Maximum allowable phase imbalance is: voltage, 2
%
;
amps 10
%
.
2. All units/modules have dual point primary power connection. (Each
unit/module requires its own power supply.) Main power must be sup-
plied from a field-supplied disconnect.
3. The unit control circuit power transformer (24 v, single-phase for all
voltages) is factory supplied.
4. Cooler heaters are wired into the main power circuit so they are always
operable as long as the disconnect is on, even if any safety device is
open, and the unit ON/OFF switch is in the OFF position.
PUMP ELECTRICAL DATA
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed minimum and max-
imum limits. Maximum allowable phase imbalance is: voltage, 2
%
;
amps 10
%
.
2. All units/modules have single/dual point primary power connection.
(Each unit/module requires its own power supply.) Main power must be
supplied from a field-supplied disconnect.
3. The unit control circuit power transformer (24 v, single-phase for all
voltages) is factory supplied.
4. Cooler heaters are wired into the main power circuit so they are always
operable as long as the disconnect is on, even if any safety device is
open, and the unit ON/OFF switch is in the OFF position.
UNIT
30RAP
UNIT VOLTAGE
V-Hz (3 Ph)
STANDARD CONDENSER
FANS
Quantity
FLA
(each)
070
208/230-3-60
5
6.0
380-3-60
5
3.9
460-3-60
5
2.9
575-3-60
5
2.4
0
8
0
208/230-3-60
6
6.0
380-3-60
6
3.9
460-3-60
6
2.9
575-3-60
6
2.4
090
208/230-3-60
6
6.0
380-3-60
6
3.9
460-3-60
6
2.9
575-3-60
6
2.4
UNIT
30RAP
UNIT VOLTAGE
V-Hz (3 Ph)
OPTIONAL CONDENSER
FANS
Quantity
FLA
(each)
070
208/230-3-60
5
6.6
380-3-60
5
3.9
460-3-60
5
3.3
575-3-60
5
2.6
0
8
0
208/230-3-60
6
6.6
380-3-60
6
3.9
460-3-60
6
3.3
575-3-60
6
2.6
090
208/230-3-60
6
6.6
380-3-60
6
3.9
460-3-60
6
3.3
575-3-60
6
2.6
FLA
—
Full Load Amps
30RAP SIZE
PUMP OPTION
PUMP SIZE
PUMP RPM
UNIT VOLTAGE
V-Hz (3 Ph)
FLA
(each)
010-060
2, 9
1.5 HP
3500
208/230-60
4.3
3500
380-60
2.4
3500
460-60
2.1
3500
575-60
1.6
3, 4, B, C
3.0 HP
3500
208/230-60
7.9
3500
380-60
4.4
3500
460-60
3.7
3500
575-60
3.0
5, 6, D, F
5.0 HP
3500
208/230-60
12.6
3500
380-60
7.0
3500
460-60
5.8
3500
575-60
4.6
7, G
7.5 HP
3500
208/230-60
18.5
3500
380-60
10.4
3500
460-60
8.7
3500
575-60
7.0
Z, H
10.0 HP
3500
208/230-60
25.0
3500
380-60
14.0
3500
460-60
11.5
3500
575-60
9.2
070-090
1, 6, C, J
3.0 HP
3500 (Single)
1750 (Dual)
208/230-60
10.8
380-60
5.9
460-60
4.9
575-60
3.9
2, 7, D, K
5.0 HP
3500
208/230-60
17.7
380-60
9.7
460-60
8.0
575-60
6.4
3,
8
, F, L
7.5 HP
3500
208/230-60
25.7
380-60
14.0
460-60
11.6
575-60
9.3
4, 9, G, M
10.0 HP
3500
208/230-60
33.6
380-60
18.4
460-60
15.2
575-60
12.2
5, B, H, N
15.0 HP
3500
208/230-60
49.8
380-60
27.2
460-60
22.5
575-60
18.0
FLA
—
Full Load Amps
Electrical data (cont)
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...
Page 75: ......