![Carrier Aquasnap 30RAP010 Product Data Download Page 55](http://html1.mh-extra.com/html/carrier/aquasnap-30rap010/aquasnap-30rap010_product-data_2561845055.webp)
55
MAXIMUM FIELD WIRING SIZES
LEGEND
UNIT INCOMING POWER OPTIONS
LEGEND
NOTES:
1. Terminal block high SCCR option units must use approved fuses
to meet high SCCR rating.
2. High disconnect SCCR option units can use either approved fuse
or circuit breaker for incoming power protection.
3. Time delay fuse type required.
ACCESSORY TANK ELECTRICAL DATA FOR 30RAP010-060 ONLY
LEGEND
NOTE: The storage tank obtains its power from the chiller. No separate
power source is required.
CONNECTION TYPE
MCA RANGE
WIRE SIZE RANGE
TERMINAL BLOCK
MCA up to 175 Amps
14 AWG to 2/0 AWG
MCA 176 to 760 Amps
2 AWG to 600 kcmil
NON-FUSED DISCONNECT
MCA up to 100 Amps
14 AWG to 1/0 AWG
MCA 101 to 200 Amps
6 AWG to 350 kcmil
MCA 200 to 600 Amps
3/0 AWG to 500 kcmil
AWG —
American Wire Gage
MCA —
Minimum Circuit Amps
MOCP VALUE
UNIT INCOMING POWER OPTION
Standard Terminal
Block Option
High SCCR Terminal Block Option
Standard and High SCCR
Terminal Block Option
Max. Wire
Size
Min. Wire
Size
Max. Wire
Size
Min. Wire
Size
High SCCR
Fuse type
Max. Wire
Size
Min. Wire
Size
100 A or Less
2/0
#14 AWG
2/0
#6 AWG
J, RK1, or RK5
1/0
#14 AWG
Greater than 100 A
and Less than 200 A
2/0
#14 AWG
2/0
#6 AWG
J or RK1
350 kcmil
#6 AWG
Greater than 200 A
600 kcmil
#2 AWG
600 kcmil
3/0
J or RK1
500 kcmil (1)
500 kcmil (2)
3/0
AWG
—
American Wire Gage
kcmil
—
Thousand Circular Mils
MOCP —
Maximum Overcurrent Protection
SCCR —
Short Circuit Current Rating
UNIT VOLTAGE
(V-Hz)
ACCESSORY PART NO.
30RA-900---
FLA
20
8
/230-60
050
11.3
051
11.3
052
22.6
460-60
050
5.7
051
5.7
052
11.3
575-60
050
7.1
051
7.1
052
14.1
3
8
0-60
050
4.7
051
4.7
052
9.3
FLA
—
Full Load Amps
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...
Page 75: ......