5
LEGEND
* Air Conditioning, Heating, and Refrigeration Institute.
NOTE: Based on AHRI-550/590 standard rating conditions. Ratings are for
standard chillers only. Ratings do not include options.
UNIT
30RAP
CAPACITY
COMPRESSOR
POWER INPUT
(kW)
FAN
POWER
(kW)
TOTAL
POWER
(kW)
FULL LOAD
IPLV
COOLER FLOW
RATE
COOLER
WATER
PRESSURE
DROP
Tons
kW
EER
COP
EER
COP
GPM
L/s
Ft wg
kPa
010
10.5
36.8
10.7
1.2
12.0
10.5
3.1
14.2
4.2
25.1
1.6
13.7
40.9
015
14.0
49.2
15.6
1.3
16.8
10.0
2.9
13.2
3.9
33.5
2.1
15.7
46.8
01
8
16.1
56.6
15.6
3.0
18.6
10.4
3.0
14.5
4.2
38.6
2.4
15.6
46.5
020
18.8
66.1
19.1
2.9
21.9
10.3
3.0
14.5
4.2
45.2
2.9
14.2
42.4
025
23.4
82.3
24.5
2.8
27.4
10.3
3.0
15.3
4.5
56.3
3.6
17.8
53.1
030
27.6
97.1
30.9
2.7
33.6
9.9
2.9
14.8
4.3
66.3
4.2
20.9
62.3
035
34.4
121.0
35.9
3.8
39.7
10.4
3.0
14.9
4.4
82.5
5.2
13.2
39.4
040
38.9
136.8
42.3
3.8
46.1
10.1
3.0
15.3
4.5
93.4
5.9
13.8
41.2
045
43.1
151.6
48.6
3.4
52.0
10.0
2.9
15.3
4.5
103.4
6.5
15.3
45.6
050
47.3
166.3
53.1
3.8
57.0
10.0
2.9
14.7
4.3
113.5
7.2
19.1
57.0
055
51.8
182.2
56.4
5.3
61.7
10.1
3.0
14.6
4.3
124.2
7.8
17.6
52.5
060
56.0
196.9
60.8
5.3
66.2
10.2
3.0
14.5
4.2
134.4
8.5
20.5
61.2
070
68.9
242.3
74.6
6.8
81.4
10.2
3.0
15.2
4.5
165.2
10.4
19.5
59.4
0
8
0
77.4
272.2
83.2
6.7
89.9
10.3
3.0
15.5
4.5
185.9
11.7
21.2
52.5
090
84.0
295.4
91.0
6.8
97.8
10.3
3.0
15.9
4.7
201.7
12.7
22.7
65.6
COP —
Coefficient of Performance
EER —
Energy Efficiency Ratio
IPLV —
Integrated Part Load Value
AHRI* capacity ratings
Summary of Contents for Aquasnap 30RAP010
Page 14: ...14 a30 5349 Base unit dimensions 30RAP070 090...
Page 15: ...15 ACCESSORY STORAGE TANK FOR UNIT SIZES 010 015 a30 4879 Accessory dimensions...
Page 16: ...16 ACCESSORY STORAGE TANK FOR UNIT SIZES 018 030 a30 4880 Accessory dimensions cont...
Page 17: ...17 ACCESSORY STORAGE TANK FOR UNIT SIZES 035 060 a30 4881...
Page 60: ...60 600 760 a30 5264 Typical control wiring schematic...