
68
Table 10 — Bolt Torque Requirements, Foot Pounds
Leak Test Chiller —
Due to regulations regarding refrig-
erant emissions and the difficulties associated with separating
contaminants from the refrigerant, Carrier recommends the
following leak test procedure. Refer to Tables 11A and 11B for
refrigerant pressure/temperature values.
1. If the pressure readings are normal for the chiller
condition:
a. Evacuate the holding charge from the vessels, if
present.
b. Raise the chiller pressure, if necessary, by adding
refrigerant until pressure is at the equivalent satu-
rated pressure for the surrounding temperature.
Follow pumpout procedures in the Transfer Refrig-
erant from Storage Tank Vessel to Chiller section,
c. Leak test chiller as outlined in Steps 3 - 9.
2. If the pressure readings are abnormal for the chiller con-
dition:
a. Prepare to leak test chillers shipped with refriger-
ant (Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap
test all joints. If the test pressure holds for 30 minutes,
prepare the test for small leaks (Steps 2g - h).
c. Plainly mark any leaks that are found.
d. Release the pressure in the system.
e. Repair all leaks.
f. Retest the joints that were repaired.
g. After successfully completing the test for large
leaks, remove as much nitrogen, air, and moisture
as possible, given the fact that small leaks may be
present in the system. This can be accomplished by
following the dehydration procedure, outlined in
the Chiller Dehydration section, page 71.
h. Slowly raise the system pressure to a maximum of
160 psig (1103 kPa) but no less than 35 psig
(241 kPa) for HFC-134a by adding refrigerant.
Proceed with the test for small leaks (Steps 3-9).
3. Check the chiller carefully with an electronic leak detec-
tor or soap bubble solution.
4. Leak Determination — If an electronic leak detector indi-
cates a leak, use a soap bubble solution, if possible, to
confirm. Total all leak rates for the entire chiller. Leakage
at rates greater than 0.1% of the total charge per year must
be repaired. Note the total chiller leak rate on the start-up
report.
5. If no leak is found during the initial start-up procedures,
complete the transfer of refrigerant gas from the pumpout
storage tank to the chiller. Retest for leaks.
BOLT SIZE
(IN.)
SAE 2, A307 GR A
HEX HEAD
NO MARKS
LOW CARBON STEEL
SAE 5, SA449
SOCKET HEAD OR HEX
WITH 3 RADIAL LINES
MEDIUM CARBON STEEL
SAE 8, SA354 GR BD
HEX HEAD
WITH 6 RADIAL LINES
MEDIUM CARBON STEEL
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
1
/
4
4
6
6
9
9
13
5
/
16
8
11
13
18
20
28
3
/
8
13
19
22
31
32
46
7
/
16
21
30
35
50
53
75
1
/
2
32
45
53
75
80
115
9
/
16
46
65
75
110
115
165
5
/
8
65
95
105
150
160
225
3
/
4
105
150
175
250
260
370
7
/
8
140
200
265
380
415
590
1
210
300
410
580
625
893
1
1
/
8
330
475
545
780
985
1,410
1
1
/
4
460
660
770
1,100
1,380
1,960
1
3
/
8
620
885
1,020
1,460
1,840
2,630
1
1
/
2
740
1060
1,220
1,750
2,200
3,150
1
5
/
8
1010
1450
1,670
2,390
3,020
4,310
1
3
/
4
1320
1890
2,180
3,110
3,930
5,610
1
7
/
8
1630
2340
2,930
4,190
5,280
7,550
2
1900
2720
3,150
4,500
5,670
8,100
2
1
/
4
2180
3120
4,550
6,500
8,200
11,710
2
1
/
2
3070
4380
5,000
7,140
11,350
16,210
2
3
/
4
5120
7320
8,460
12,090
15,710
22,440
3
6620
9460
11,040
15,770
19,900
28,440
WARNING
Do not use air or oxygen as a means of pressurizing the
chiller. Mixtures of HFC-134a and air can undergo
combustion.
WARNING
Never charge liquid refrigerant into the chiller if the pres-
sure in the chiller is less than 35 psig (241 kPa) for HFC-
134a. Charge as a gas only, with the cooler and condenser
pumps running, until this pressure is reached, using
PUMPDOWN LOCKOUT and TERMINATE LOCK-
OUT mode on the PIC II. Flashing of liquid refrigerant at
low pressures can cause tube freeze-up and considerable
damage.
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...