19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Comp Motor Temp Override
150 to 200
66 to 93
DEG F
DEG C
200
93
Cond Press Override
90 to 165
621 to 1138
PSI
kPa
125
862
Comp Discharge Alert
125 to 200
52 to 93
DEG F
DEG C
200
93
Comp Thrust Brg Alert
10 to 20
6 to 11
ˆF
ˆC
10
6
Comp Thrust Brg Trip
160 to 185
71 to 85
DEG F
DEG C
185
85
Thrust Brg Reset Factor
1.0 to 3.0
1.4
Chilled Medium
0/1
WATER/BRINE
WATER
Chilled Water Deadband
0.5 to 2.0
0.3 to 1.1
ˆF
ˆC
1.0
0.6
Evap Refrig Trippoint
0.0 to 40.0
-17.8 to 4.4
DEG F
DEG C
33
0.6
Refrig Override Delta T
2.0 to 5.0
1.1 to 2.8
ˆF
ˆC
3
1.7
Evap Approach Alert
0.5 to 15
1.1 to 2.8
ˆF
ˆC
5
2.8
Cond Approach Alert
0.5 to 15
0.3 to 8.3
ˆF
ˆC
6
3.3
Condenser Freeze Point
–20 to 35
-28.9 to 1.7
DEG F
DEG C
34
1.1
Flow Delta P Display
0/1
DSABLE/ENABLE
DSABLE
Evap Flow Delta P Cutout
0.5 to 50.0
3.4 to 344.8
ˆPSI
ˆkPa
5.0
34.5
Cond Flow Delta P Cutout
0.5 to 50.0
3.4 to 344.8
ˆPSI
ˆkPa
5.0
34.5
Cond Hi Flow Alarm Option
0/1
DSABLE/ENABLE
DSABLE
Cond Hi Flow Del P Limit
0.5 to 50.0
3.4 to 344.8
PSI
kPa
50.0
344.8
Water Flow Verify Time
0.5 to 5
MIN
5
Oil Press Verify Time
15 to 300
SEC
40
Recycle Control
Restart Delta T
2.0 to 10.0
1.1 to 5.6
ˆF
ˆC
5
2.8
Shutdown Delta T
0.5 to 4.0
0.3 to 2.2
ˆF
ˆC
1
0.6
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
0 to 4
0
Spare Temp #1 Limit
–40 to 245
–40 to 118
DEG F
DEG C
245
118
Spare Temp #2 Enable
0 to 4
0
Spare Temp #2 Limit
–40 to 245
–40 to 118
DEG F
DEG C
245
118
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...