Table 3 — ICVC Display Data (cont)
EXAMPLE 15 — WSMCHRLE DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
5. Scroll down to highlight
.
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
EXAMPLE 16 — NET_OPT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
5. Scroll down to highlight
.
6. Press .
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION
STATUS
UNITS
POINT
WSM Active?
0/1
NO/YES
WSMSTAT
Chilled Water Temp
0.0-99.9
DEG F
CHWTEMP
Equipment Status
0/1
OFF/ON
CHWRST
Commanded State
XXXXXXXX
TEXT
CHLRENA
CHW setpt Reset Value
0.0-25.0
DEG F
CHWRVAL
Current CHW Set Point
0.0-99.9
DEG F
CHWSTPT
DESCRIPTION STATUS UNITS POINT
DEFAULT
Loadshed Function
Group Number
0-99
ldsgrp
0
Demand Limit Decrease
0-60
% ldsdlta
20
Maximum Loadshed Time
0-120
MIN
maxshed
60
CCN Occupancy Config:
Schedule Number
3-99
occ_num
3
Broadcast Option
0-1
DSABLE/ENABLE
occbrcst
DSABLE
Alarm Configuration
Re-Alarm Time
0-1440
MIN
retime
30
Alarm Routing
xxxxxxxx
routing
10000000
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
WSMCHRLE
SELECT
MENU
SERVICE
EQUIPMENT CONFIGURATION
SELECT
NET_OPT
SELECT
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...