148
CAUTION
USE COPPER CONDUCTORS ONLY
UTILISEZ DES CONDUCTEURS EN CUIVRE SEULMENT
ALWAYS USE 2 WRENCHES TO TIGHTEN
• TERM INSULATOR TO MOTOR – 15-35 ft. lb.
• BRASS NUT TO TERM INSULATOR – 3 ft. lb. max
• ADAPTOR TO TERM STUD – 20-35 ft. lb.
• LUG BOLTS (1/2")– 32-45 ft. lb.
Insulate entire connection with electrical insulation
including 1 inch of cable insulation and 1 inch of the
term insulator.
!
TERMINAL STUD
INSULATION
ADAPTER
BRASS NUT
TERMINAL
INSULATOR
1
2
3
13
CAUTION
USE COPPER CONDUCTORS ONLY
UTILISEZ DES CONDUCTEURS EN CUIVRE SEULMENT
ALWAYS USE 2 WRENCHES TO TIGHTEN
• TERM INSULATOR TO MOTOR – 15-35 ft. lb.
• CABLE LUG NUT – 40-45 ft. lb.
Insulate entire connection with electrical insulation
including 1 inch of cable insulation and 1 inch of the
term insulator.
!
TAPE TO EXTEND TO AND OVER
LEAD WIRE INSULATION
AFTER ATTACHING LEAD, THIS AREA
TO BE WRAPPED WITH ONE LAYER OF
THERMAL INSULATION PUTTY AND AT
LEAST FOUR LAYERS OF APPROPRIATE
ELECTRICAL INSULATING TAPE.
1
2
3
12
6
4
5
MOTOR LEAD INSTALLATION LABELS
19XR,XRV COMPRESSOR ASSEMBLY TORQUES FRAME 2-5
* Not shown.
19XR,XRV COMPRESSOR ASSEMBLY TORQUES FRAME E
Fig. 60 — Compressor Assembly Torques — Single and Two-Stage Compressors
ITEM
COMPRESSOR
FRAME 2
FRAME 3
FRAME 4
FRAME 5
CODE
201-299, 2ZZ
321-389, 3ZZ,
32E-38H
421-487, 4B1-4W7
501-599
1
Oil Heater Retaining Nut — ft-lb (N·m)
N/A
18-22 (25-30)
18-22 (25-30)
18-22 (25-30)
2
Bull Gear Retaining Bolt — ft-lb (N·m)
80-90 (108-122)
80-90 (108-122)
80-90 (108-122)
80-90 (108-122)
3
Demister Bolts — ft-lb (N·m)
15-19 (20-26)
15-19 (20-26)
15-19 (20-26)
15-19 (20-26)
4
Impeller bolt Torque — ft-lb (N·m)
32-48 (43-65)
55-60 (75-81)
55-60 (75-81)
160-225 (217-305)
5*
Guide Vane Shaft Seal Nut — ft-lb (N·m)
25 (34)
25 (34)
25 (34)
25 (34)
ITEM
COMPRESSOR
FRAME 2
CODE
E31-E69
1
Oil Heater Retaining Nut — ft-lb (N·m)
18-22 (24-30)
2
Bull Gear Retaining Bolt — ft-lb (N·m)
80-90 (108-122)
3
Demister Bolts — ft-lb (N·m)
15-19 (20-26)
4
Impeller Nut (Inner) — ft-lb (N·m)
250 (339)
5
Impeller Nut (Outer) — ft-lb (N·m)
100 (136)
6*
Guide Vane Shaft Seal Nut — ft-lb (N·m)
25 (34)
a19-1642
a19-1643
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...