19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Auto Restart Option
0/1
DSABLE/ENABLE
DSABLE
Guide Vane Closure
4 to 25
%
4
Remote Contacts Option
0/1
DSABLE/ENABLE
DSABLE
Soft Stop Amps Threshold
40 to 100
%
100
Surge / Hot Gas Bypass
Surge Limit/HGBP Option
0, 1, 2
0
Select: Surge=0, HGBP=1
Low Load HGBP=2
Minimum Load Point
Surge/HGBP Delta Tsmin
0.0 to 150.0
ˆF
45
Surge/HGBP IGVmin
0.0 to 110.0
%
5.0
Full Load Point
Surge/HGBP Delta Tsmax
0.0 to 150.0
ˆF
70
Surge/HGBP IGVmax
0.0 to 110.0
%
5.0
Surge Line Shape Factor
–1.000 to 0.000
–0.040
Surge Line Speed Factor
0.00 to 3.00
1.85
Surge Line High Offset
0.1 to 3.0
1.0
Surge/HGBP Deadband
0.5 to 3
ˆF
1
HGBP On Delta T
0.5 to 10.0
ˆF
2.0
HGBP Off Delta T
0.5 to 10.0
ˆF
4.0
Surge Protection
Surge Delta% Amps
5 to 40
%
20
Surge Time Period
7 to 10
MIN
8
Surge Delay Time
0 to 120
SEC
0
Ice Build Control
Ice Build Option
0/1
DSABLE/ENABLE
DSABLE
Ice Build Termination
0 to 2
0
0=Temp, 1=Contact, 2=Both
Ice Build Recycle
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Option
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Alarm mA
4 to 20
mA
20
Head Pressure Reference
Delta P at 0% (4mA)
20 to 85
PSI
25
Delta P at 100% (20mA)
20 to 85
PSI
50
Minimum Output
0 to 100
%
0
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...