Table G — UPC Open Points List for Version 14 19XR Software (cont)
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
System Alert/Alarm
SYS_ALM
R
1=Normal
2=Alert
3=Alarm
AV:40
sys_alm_1
System Cooling Demand Level
N/A
R
AV:9006
cool_de-
mand_level_1
System Demand Limiting
N/A
R
BV:3
dem_lmt_act_1
Target Guide Vane Position
GV_TRG
R
%
AV:41
gv_trg_1
Target VFD Speed
VFD_OUT
R
%
AV:42
vfd_out_1
Twr Fan Relay High
TFR_LOW
R
BV:13
tfr_high_1
Twr Fan Relay Low
TFR_HIGH
R
BV:14
tfr_low_1
User Defined Analog 1
N/A
R
AV:2901
user_analog_1_1
User Defined Analog 2
N/A
R
AV:2902
user_analog_2_1
User Defined Analog 3
N/A
R
AV:2903
user_analog_3_1
User Defined Analog 4
N/A
R
AV:2904
user_analog_4_1
User Defined Analog 5
N/A
R
AV:2905
user_analog_5_1
User Defined Binary 1
N/A
R
BV:2911
user_binary_1_1
User Defined Binary 2
N/A
R
BV:2912
user_binary_2_1
User Defined Binary 3
N/A
R
BV:2913
user_binary_3_1
User Defined Binary 4
N/A
R
BV:2914
user_binary_4_1
User Defined Binary 5
N/A
R
BV:2915
user_binary_5_1
CHW
— Chilled Water
R
— Read
VFD
— Variable Frequency Drive
W
— Write
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...