33
Table 3 — ICVC Display Data (cont)
EXAMPLE 7 — ISM_STAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation.
EXAMPLE 8 — ICVCPSWD DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press
.
3. Scroll down to highlight
4. Press .
NOTES:
1. All variables with CAPITAL LETTER point names are available
for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
2. To Disable Service Password, force that item to a value of “1”
using Service Tool. Once this has been done, the Service menu
and the ISM (Starter) Config Data screens can be accessed
without a password. This access is cancelled at the time the
user exits the Service menu/screen.
3. If the Remote Reset Option is set to a value of “1” at the ICVC,
alarms may be reset and CCN mode may be reinstated
remotely using Service Tool, Building Supervisor, or Comfort-
WORKS
®
controls.
DESCRIPTION
STATUS
UNITS
POINT
ISM Fault Status
0-255
ISMFLT
Single Cycle Dropout
0-1
NORMAL/ALARM
CYCLE_1
Phase Loss
0-1
NORMAL/ALARM
PH_LOSS
Overvoltage
0-1
NORMAL/ALARM
OV_VOLT
Undervoltage
0-1
NORMAL/ALARM
UN_VOLT
Current Imbalance
0-1
NORMAL/ALARM
AMP_UNB
Voltage Imbalance
0-1
NORMAL/ALARM
VOLT_UNB
Overload Trip
0-1
NORMAL/ALARM
OVERLOAD
Locked Rotor Trip
0-1
NORMAL/ALARM
LRATRIP
Starter LRA Trip
0-1
NORMAL/ALARM
SLRATRIP
Ground Fault
0-1
NORMAL/ALARM
GRND_FLT
Phase Reversal
0-1
NORMAL/ALARM
PH_REV
Frequency Out of Range
0-1
NORMAL/ALARM
FREQFLT
ISM Power on Reset
0-1
NORMAL/ALARM
ISM_POR
Phase 1 Fault
0-1
NORMAL/ALARM
PHASE_1
Phase 2 Fault
0-1
NORMAL/ALARM
PHASE_2
Phase 3 Fault
0-1
NORMAL/ALARM
PHASE_3
1CR Start Complete
0-1
FALSE/TRUE
START_OK
1M Start/Run Fault
0-1
NORMAL/ALARM
1M_FLT
2M Start/Run Fault
0-1
NORMAL/ALARM
2M_FLT
Pressure Trip Contact
0-1
NORMAL/ALARM
PRS_TRIP
Starter Fault
0-1
NORMAL/ALARM
STRT_FLT
Motor Amps Not Sensed
0-1
NORMAL/ALARM
NO_AMPS
Starter Acceleration Fault
0-1
NORMAL/ALARM
ACCELFLT
High Motor Amps
0-1
NORMAL/ALARM
HIGHAMPS
1CR Stop Complete
0-1
FALSE/TRUE
STOP_OK
1M/2M Stop Fault
0-1
NORMAL/ALARM
1M2MSTOP
Motor Amps When Stopped
0-1
NORMAL/ALARM
AMPSTOP
Hardware Failure
0-1
NORMAL/ALARM
HARDWARE
MENU
STATUS
ISM_STAT
SELECT
DESCRIPTION
STATUS
UNITS
POINT
Disable Service Password
0-1
DSABLE/ENABLE
PSWD_DIS
**Remote Reset Option (See Note 3)
0-1
DSABLE/ENABLE
RESETOPT
Reset Alarm?
0-1
NO/YES
REMRESET
CCN Mode?
1
YES
REM_CCN
MENU
STATUS
ICVC
SELECT
Summary of Contents for AquaEdge 19XR series
Page 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Page 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Page 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Page 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Page 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Page 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...