WARNING: If the Manual Reset is active, a consecutive Input have to be used. Example
: Input 1 and Input 2 are used for the fuctional block, then Input 3 have to be used for
the Reset Input.
OUT TEST signals cannot be used in case of safety static output ESPE because the control
is carried out from the ESPE.
Test at start-up: If selected this enables the test at start-up of the safety light curtain. This
test
is performed by occupying and clearing the area protected by the safety light curtain to run
a complete function test and enable the output. This test is only requested at machine startup
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the safety light curtain. The filter can
be configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit’s total response time.
With Contemporaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the safety light curtain.
Contemporaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the safety light
curtain.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component’s function to be entered.
The text is displayed in the top part of the symbol.