30
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 07/18
CERTUS Installation Manual
Technical Features
General System Characteristics
Safety Level Parameters
Parameter
Value
Standard
PFHd
See the technical data tables for each module
IEC 61508:2010
SIL
3
SFF
99,8%
HFT
1
Safety Standard
Type B
SILCL
3
IEC 62061:2005
Type
4
EN 61496-1: 2013
PL
e
EN ISO 13849-1:2008
EN 62061:2005
Dcavg
High
MTTFd (years)
30÷100
Category
4
Device lifetime
20 years
Pollution degree
2
General Data
Max number of inputs
128
Max number of outputs
16
Max number of slave units
(excluding C 2R - C 4R)
14
Max number of slave units of the
same type (excluding C 2R - C 4R)
4
Rated voltage
24VDC ± 20% / Supply from class II (LVLE)
Over voltage category
II
Digital INPUTS
PNP active high (EN 61131-2)
OSSD (CMM, C 8I 2O, C 2OSSD, C 4OSSD)
PNP active high - 400mA@24VDC max (each OSSD)
Digital OUTPUTS
PNP active high - 100mA@24VDC max
Response time (ms)
This response times depends on the
following parameters:
1) Number of Slave modules installed
2) Number of Operators
3) Number of OSSD outputs
Failure Response time (ms)
This parameter corresponds to the response
time, with the exception of C ES modules
with Encoder/Proximity inerface where is 2s.
Master
10,6 ÷ 12,6
+ TInput_filter
CMM + 1 Slave
11,8 ÷ 26,5
+ TInput_filter
CMM + 2 Slave
12,8 ÷ 28,7
+ TInput_filter
CMM + 3 Slave
13,9 ÷ 30,8
+ TInput_filter
CMM + 4 Slave
15 ÷ 33
+ TInput_filter
CMM + 5 Slave
16 ÷ 35
+ TInput_filter
CMM + 6 Slave
17 ÷ 37,3
+ TInput_filter
CMM + 7 Slave
18,2 ÷ 39,5
+ TInput_filter
CMM + 8 Slave
19,3 ÷ 41,7
+ TInput_filter
CMM + 9 Slave
20,4 ÷ 43,8
+ TInput_filter
CMM + 10 Slave
21,5 ÷ 46
+ TInput_filter
CMM + 11 Slave
22,5 ÷ 48,1
+ TInput_filter
CMM + 12 Slave
23,6 ÷ 50,3
+ TInput_filter
CMM + 13 Slave
24,7 ÷ 52,5
+ TInput_filter
CMM + 14 Slave
25,8 ÷ 54,6
+ TInput_filter
CMM> module connection
Carlo Gavazzi proprietary 5-pole bus (SCC)
Connection cable cross-section
0,5 ÷ 2,5 mm
2
/ AWG 12÷30 (solid/stranded)
Max length of connections
100m
Operating temperature
-10 ÷ 55°C
Max surrounding air temperature
55°C (UL)
Storage temperature
-20 ÷ 85°C
Relative humidity
10% ÷ 95%
Max. altitude (above sea level)
2000m