Filter (ms): This is used to filter the signals coming from the emergency stop. The filter can be
configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit’s total response time.
With Contemporaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the emergency stop.
Contemporaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the emergency
stop.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component’s function to be entered.
The text is displayed in the top part of the symbol.
E-GATE (safety device)
E-GATE function block verifies a mobile guard
or safety gate device input status. If the mobile
guard or safety gate is open, the output is 0
(FALSE). Otherwise the output is 1 (TRUE).
Parameters
Input type:
- Double NC – Allows connection of components
with two NC contacts
- Double NC/NO – Allows connection of
components with one NO contact and one NC.
Enable reset: If selected this enables the request
to reset each time the mobile guard/safety gate
is activated. Otherwise, enabling of the output
directly follows the input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system only verifies the signal’s transition from 0 to 1
Parameters If Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.