The MUTING operator with “T” logic
performs muting of the input signal through
sensor inputs S1 and S2.
Muting “T”
⇒
Preliminary condition: The Muting
cycle can only start if S1 and S2 are
0 (FALSE) and the inputs are 1 (TRUE)
(barrier free).
Parameters
Timeout (sec):
Sets the time, between 10 secs and unlimited, within which the Muting
cycle must end. If the cycle is not complete at the end of this time, Muting is immediately
discontinued.
Enable:
If selected it enables the possibility of enabling or not enabling the Muting function.
Otherwise the Muting function is always enabled. There are two Enable modes: Enable/
Disable and Enable Only. If Enable/Disable is selected the Muting cycle cannot start if Enable
is fixed at 1 (TRUE) or 0 (FALSE) but is only activated with a rising edge. To disable muting,
set Enable to 0 (FALSE). In this mode the falling edge disables Muting regardless of the
condition. If Enable Only is selected Muting cannot be disabled but Enable must be set to 0
(FALSE) in order to enable a new rising edge for the next muting cycle.
Sensor time: A difference of between 2 and 5 seconds can be set for activating the sensors.