94
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Supervisor table
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM
Description
35
1
U025
INT
0..2
R/W
U025 - Analogue set point input type (0 = 0-5V, 1 = 0-10V, 2 = 4-20mA)
37
2
U026
REAL
-99.9..99.9
R/W
°C/°F
U026 - Minimum remote set point value
39
2
U027
REAL
-99.9..99.9
R/W
°C/°F
U027 - Max remote set point value
41
1
S023
INT
0..23
R/W
h
Time band hours
42
1
S024
INT
0..59
R/W
min
Time band minutes
43
2
U028
REAL
-99.9..99.9
R/W
K/R
U028 - Remote set point off set
48
1
E046
INT
1..24
R/W
E046 - ExV valve type for EVD EVO (1 = CAREL EXV, ...)
49
2
U031
REAL
0..99.9
R/W
K/R
U031– High water temp. alarm: off set
51
1
U032
INT
0..99
R/W
min
U032 – High water temp. alarm: delay at start-up
52
1
U033
INT
0 to 999
R/W
s
U033 – High water temp. alarm: delay when running
53
1
U035
INT
0 to 999
R/W
min
U035 - Changeover delay time
54
1
U037
INT
0 to 999
R/W
s
U037 - Delay time between Startup PID and Run PID
55
2
U039
REAL
0..999.9
R/W
U039 - Startup PID Kp
57
1
U040
INT
0 to 999
R/W
s
U040 - PID at start-up Ti
58
1
U041
INT
0..99
R/W
s
U041 - Startup PID Td
59
2
U042
REAL
0..999.9
R/W
U042 - Kp for PID when running
61
1
U043
INT
0 to 999
R/W
s
U043 - Ti for PID when running
62
1
U044
INT
0..99
R/W
s
U044 - Td for PID when running
63
1
U045
INT
0 to 999
R/W
s
U045 - User pump fl ow alarm delay at start-up
64
1
U046
INT
0..99
R/W
s
U046 - User pump fl ow alarm delay when running
65
1
U047
INT
0 to 999
R/W
s
U047 - Comp. ON delay from user pump ON
66
1
U048
INT
0 to 999
R/W
s
U048 - User pump OFF delay from comp. OFF
67
1
U049
INT
0 to 999
R/W
h
U049 - User pump rotation time
68
2
U050
REAL
-999.9..999.9
R/W
°C/°F
U050 - User frost protection alarm threshold
70
2
U051
REAL
0..999.9
R/W
K/R
U051 - User frost protection alarm diff erential
72
1
U052
INT
0 to 999
R/W
s
U052 - User frost protection alarm delay at 1K below the threshold
73
2
U053
REAL
-999.9..999.9
R/W
°C/°F
U053 - Frost protection set point (with unit OFF)
75
2
U054
REAL
0..99.9
R/W
K/R
U054 - Frost protection diff erential (with unit OFF)
78
1
DFr
INT
0..3
R/W
DFr - Force manual defrost (0 = None, 1 = Force defrost circuit 1, 2 = Force defrost
circuit 2, 3 = Force defrost on all circuits)
79
2
U055
REAL
-99.9..99.9
R/W
K/R
U055 - User return water temp. probe off set
83
2
U056
REAL
-99.9..99.9
R/W
K/R
U056 - User delivery water temp. probe off set
85
2
U069
REAL
0..99.9
R/W
K/R
U069 - Temp. diff erential to activate free cooling
87
2
U070
REAL
0..99.9
R/W
K/R
U070 - Free cooling ON/OFF hysteresis
89
2
U071
REAL
0..99.9
R/W
K/R
U071 - Design free cooling temp. diff erential (to reach unit rated capacity)
91
2
U072
REAL
-999.9..999.9
R/W
°C/°F
U072 - Free cooling limit threshold (used to close the FC valve: because FC supplies
water at very low temp.)
93
2
U073
REAL
0..99.9
R/W
K/R
U073 - Free cooling limit diff erential
95
1
U074
INT
0..2
R/W
U074 - Free cooling type (0 = Air, 1 = Remote air coil, 2 = Water)
96
1
U075
INT
0..2
R/W
U075 - Frost protection type (0 = Heater, 1 = Pump, 2 = Heater/pump)
97
1
U076
INT
1..2
R/W
U076 - Number of user pumps
98
1
U077
INT
0..2
R/W
U077 - Type of unit (0 = CH, 1 = HP, 2 = CH/HP)
99
1
E001
INT
0..65535
R/W
Steps
E001 – ExV: Steps in manual mode circ. 1
100
1
E003
INT
0..65535
R/W
Steps
E003 – ExV: Steps in manual mode circ. 2
101
2
E004
REAL
-40..180
R/W
K/R
E004 – ExV: SH set point in cooling
103
2
E005
REAL
0..800
R/W
E005 – ExV: SH control Kp in cooling
105
2
E006
REAL
0..1000
R/W
s
E006 – ExV: SH control Ti in cooling
107
2
E007
REAL
0..800
R/W
s
E007 – ExV: SH control Td in cooling
109
2
E008
REAL
-40..180
R/W
K/R
E008 – ExV: SH set point in heating
111
2
E009
REAL
0..800
R/W
E009 – ExV: SH control Kp in heating
113
2
E010
REAL
0..1000
R/W
s
E010 – ExV: SH control Ti in heating
115
2
E011
REAL
0..800
R/W
s
E011 – ExV: SH control Td in heating
117
2
E012
REAL
-40..180
R/W
K/R
E012 - ExV: low SH in cooling: threshold
119
2
E013
REAL
0..800
R/W
s
E013– ExV: low SH in cooling: Ti
121
2
E014
REAL
-40..180
R/W
K/R
E014 - ExV: low SH in heating: threshold
123
2
E015
REAL
0..800
R/W
s
E015 - ExV: low SH in heating: Ti
125
2
E016
REAL
-60..200
R/W
°C/°F
E016 - ExV: LOP control in cooling: threshold
127
2
E017
REAL
0..800
R/W
s
E017 - ExV: LOP control in cooling: Ti
129
2
E018
REAL
-60..200
R/W
°C/°F
E018 - ExV: LOP control in heating: threshold
131
2
E019
REAL
0..800
R/W
s
E019 - ExV: LOP control in heating: Ti
133
2
E020
REAL
-60..200
R/W
°C/°F
E020 - ExV: MOP control in cooling: threshold
135
2
E021
REAL
0..800
R/W
s
E021 - ExV: MOP control in cooling: Ti
137
2
E022
REAL
-60..200
R/W
°C/°F
E022 - ExV: MOP control in heating: threshold
139
2
E023
REAL
0..800
R/W
s
E023 - ExV: MOP control in heating: Ti
141
1
E024
INT
0..18000
R/W
s
E024 - ExV: low SH alarm delay
142
1
E025
INT
0..18000
R/W
s
E025 - ExV: LOP alarm delay time
143
1
E026
INT
0..18000
R/W
s
E026 - ExV: MOP alarm delay time
144
1
E032
INT
0..100
R/W
%
E032 –ExV: % valve opening at start-up (EVAP / EEV capacity ratio) in cooling
145
1
E033
INT
0..100
R/W
%
E033 –ExV: % valve opening at start-up (EVAP / EEV capacity ratio) in heating
146
1
E034
INT
0..18000
R/W
s
E034 - ExV: control delay after pre-positioning
147
1
Hd00
INT
1..247
R/W
Hd00 - BMS port serial address
148
1
Hd01
INT
3..7
R/W
Hd01 - BMS port baud rate
(3 = 9600, 4 = 19200, 5 = 38400, 6 = 57600, 7 = 115200)
149
1
Hd02
INT
0..5
R/W
Hd02 - BMS network port settings
(0 = 8- NONE- 1, 1 = 8- NONE- 2, 2 = 8- EVEN- 1, 3 = 8-EVEN-2, 4 = 8-ODD-1, 5 = 8
-ODD-2)