μc0300053EN rel. 2.2 - 14.12.2021
Functions
5.1.2 Proportional
control
If the desired control is only proportional to the water outlet or return temperature, consider the relationship:
For example, to have a proportional band of 2K, set the value of Kp to 50.
The following are the parameter settings required to control the return temperature:
User
C
od.
Description
S
etting
U
O
M
N
ote
S
U036
Control probe at start-up - 0=Return 1=Delivery
0
-
-
S
U037
PID control delay at start-up/operation
180
s
Not signifi cant
S
U038
Control probe in operation - 0=Return 1=Delivery
0
-
S
U039
PID at start-up: Kp
50.0
-
=> Proportional band = 2K
34.0
=> Proportional band = 3K
25.0
=> Proportional band = 4K
20.0
=> Proportional band = 5K
S
U040
PID at start-up: Ti - 0: integral action disabled
0
s
S
U041
PID at start-up: Td - 0: derivative action disabled
0
s
S
U042
PID in operation: Kp
=U039
s
Same as Kp at start-up
S
U043
PID in operation: Ti - 0: integral action disabled
0
s
S
U044
PID in operation: Td - 0: derivative action disabled
0
s
Tab. 5.c
5.1.3
S
et point compensation
μChiller adjusts the set point based on the outside temperature.
Notice:
this function can only be enabled if the outside temperature probe is fi tted.
The compensation (positive or negative) is determined by:
1. start compensation start (in cooling/heating);
2. end compensation threshold (in cooling/heating);
3. maximum compensation value (in cooling/heating).
User
C
ode
Description
Def
Min
Max
U
O
M
S
U010
Enable set point compensation: 0/1=no/yes
0
0
1
-
U
SEtC
Cooling set point
7.0
U006
U007
°C/°F
S
U011
Cooling compensation: start
25.0
-99.9
999.9
°C
S
U012
Cooling compensation: end
35.0
-99.9
999.9
°C
S
U013
Cooling compensation: maximum value
5.0
-99.9
999.9
K
U
SEtH
Heating set point
40.0
U008
U009
°C/°F
S
U014
Heating compensation: start
5.0
-99.9
999.9
°C
S
U015
Heating compensation: end
-10
-99.9
999.9
°C
S
U016
Heating compensation: maximum value
5.0
-99.9
999.9
K
Compensation in cooling:
Ext. temp.
Set point
Std set
T1
T2
300053_050_R01
D
T
Key
Ext. Temp.
Outside temperature
Std set
Control set point
T1
Outside temperature to start compensation in cooling mode
T2
Outside temperature to end compensation in cooling mode
DT
Maximum compensation value in cooling mode
Fig. 5.a
Compensation in heating:
Ext. temp.
Set point
Std set
T2
T1
300053_051_R01
D
T
Key
Ext. Temp.
Outside temperature
Std set
Control set point
T1
Outside temperature to start compensation in heating mode
T2
Outside temperature to end compensation in heating mode
DT
Maximum compensation value in heating mode
Fig. 5.b