60
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Functions
5.5
C
ompressor management
μChiller manages scroll compressors with direct starting or modulating BLDC compressors (scroll and rotary).
A maximum of 4 scroll compressors are available in tandem confi guration on two circuits; in the High Effi
ciency models, with
BLDC compressors, the maximum is 1BLDC+1On-Off per circuit.
The fl ow chart below shows the process for calculating the request to the compressors:
Unit ON
Pump ON
Thermoregulation
Rotation
Pump-Down
Circuit 1
Circuit 2
Envelope
prevention
Compressor
control
Temperature
control
ExV
Timings
Unit alarms
Flow alarm
BMS
Circuit alarms
0...100.0%
0...100.0%
0...100.0%
0...100.0%
0...100.0%
0...100.0%
OK pump active
OK unit ON
OK
OK
300053_013_R01
Note:
for the sake of simplicity, the
parameters are shown for just one
compressor and one circuit, therefore
all the compressors and circuits on the
unit will have the same settings.
Fig. 5.l
5.5.1 Predefi ned
B
LD
C
compressors
The type of BLDC compressor can be chosen from the list of compressors available on KSA (ksa.carel.com), μChiller section.
When selecting a specifi c type of compressor, the following parameters are set based on the compressor manufacturer’s tech-
nical specifi cations:
1. compressor
motor:
– all the characteristic electrical parameters of the compressor motor;
– minimum and maximum frequency settings, acceleration and deceleration ramps.
2. compressor
envelope:
– all the characteristic points that defi ne the shape of the compressor envelope;
– maximum discharge temperature (compressor outlet).
3. compressor envelope management:
– MOP and pressure diff erence (DeltaP), minimum ExV opening parameters;
– working point control parameters;
– prevention parameters.
5.5.2
S
afety times
μChiller guarantees compliance with compressor safety times, such as:
• minimum on time;
• minimum
off time after deactivation request from controller;
• minimum time between consecutive starts.
User
C
ode
Description
Def
Min
Max
U
O
M
M
C012
Min compressor on time
180
30
999
s
M
C013
Min compressor off time
60
30
999
s
M
C014
Min time between consecutive compressor starts
360
300
999
s