83
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Parameter table
6. PARAMETER
TABLE
Notes:
• Levels: U=User; S=Service; M=Manufacturer; Display: the x indicates that the parameter can be accessed from the display terminal;
• R/W=read/write parameters; R=read-only parameters.
6.1
S
ystem
User
Display
C
ode
Description
Def.
Min.
Max.
U
O
M
R/W
Modbus
Plt = System
S
U000
User pump 1: maintenance hour threshold (x100)
99
0
999
h
R/W
HR002
S
U001
User pump 1: reset hour counter
0
0
1
-
R/W
CS000
S
x
U002
User pump 1: operating mode
0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR003
S
U003
User pump 2: maintenance hour threshold (x100)
99
0
999
h
R/W
HR004
S
U004
User pump 2: reset hour counter
0
0
1
-
R/W
CS001
S
x
U005
User pump 2: operating mode
0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR005
S
U006
Cooling set point: minimum limit
5.0
-99.9
999.9
°C/°F
R/W
HR007 (2R)
S
U007
Cooling set point: maximum limit
20.0
-99.9
999.9
°C/°F
R/W
HR009 (2R)
S
U008
Heating set point: minimum limit
30.0
0.0
999.9
°C/°F
R/W
HR01 (2R)
S
U009
Heating set point: maximum limit
45.0
0.0
999.9
°C/°F
R/W
HR011 (2R)
S
U010
Enable set point compensation - 0/1=no/yes
0
0
1
-
R/W
CS002
S
U011
Cooling compensation: start
25.0
-99.9
999.9
°C/°F
R/W
HR015 (2R)
S
U012
Cooling compensation: end
35.0
-99.9
999.9
°C/°F
R/W
HR017 (2R)
S
U013
Cooling compensation: maximum value
5.0
-99.9
999.9
K/R
R/W
HR019 (2R)
S
U014
Heating compensation: start
5.0
-99.9
999.9
°C/°F
R/W
HR021 (2R)
S
U015
Heating compensation: end
-10
-99.9
999.9
°C/°F
R/W
HR023 (2R)
S
U016
Heating compensation: maximum value
5.0
-99.9
999.9
K/R
R/W
HR025 (2R)
S
U017
Enable time band - 0/1=No/Yes
0
0
1
-
R/W
CS003
S
U018
Time band: start hours
17
0
23
h
R/W
HR027
S
U019
Time band: start minutes
30
0
59
min
R/W
HR028
S
U020
Time band: end hours
7
0
23
h
R/W
HR029
S
U021
Time band: end minutes
0
0
59
min
R/W
HR030
S
U022
Type of changeover in time band
0=Off - 1=2nd set point
0
0
1
-
R/W
CS004
U
x
U023
2nd cooling set point
10.0
U006
U007
°C/°F
R/W
HR031(2R)
U
x
U024
2nd heating set point
35.0
U008
U009
°C/°F
R/W
HR033(2R)
S
U025
Remote set point: analogue input
0=0-5V - 1=0-10V - 2=4-20 mV
0
0
2
-
R/W
HR035
S
U026
Remote set point: min value
5.0
-99.9
999.9
°C/°F
R/W
HR037(2R)
S
U027
Remote set point: max value
35.0
-99.9
99.9
°C/°F
R/W
HR039(2R)
S
U028
Remote set point: off set
0.0
-99.9
99.9
K/R
R/W
HR043(2R)
S
x
U031
High water temp. alarm: off set
10.0
0.0
99.9
K/R
R/W
HR049(2R)
S
x
U032
High water temp. alarm: delay at start-up
15
0
99
min
R/W
HR051
S
x
U033
High water temp. alarm: delay in operation
180
0
999
s
R/W
HR052
S
U034
Operating mode changeover
0=Keypad - 1=Digital input
0
0
1
-
R/W
CS005
S
U035
Cooling/heating changeover: delay
15
0
999
min
R/W
HR053
S
U036
Control probe at start-up
0=Return - 1=Delivery
0
0
1
-
R/W
CS006
S
U037
PID control delay at start-up/operation
180
0
999
s
R/W
HR054
S
U038
Control probe in operation
0=Return - 1=Delivery
1
0
1
-
R/W
CS007
S
U039
PID at start-up: Kp
10.0
0.0
999.9
-
R/W
HR055(2R)
S
U040
PID at start-up: Ti - 0: integral action disabled
180
0
999
s
R/W
HR057
S
U041
PID at start-up: Td - 0: derivative action disabled
0
0
99
s
R/W
HR058
S
U042
PID in operation: Kp
10.0
0.0
999.9
-
R/W
HR059(2R)
S
U043
PID in operation: Ti
0: integral action disabled
120
0
999
s
R/W
HR061
S
U044
PID in operation: Td
0: derivative action disabled
3
0
99
s
R/W
HR062
S
U045
User pump fl ow alarm: delay at start-up
10
0
999
s
R/W
HR063
S
U046
User pump fl ow alarm: delay in operation
3
0
99
s
R/W
HR064
S
U047
Compressor activation delay after user pump
30
0
999
s
R/W
HR065
S
U048
User pump shutdown delay after compressor
180
0
999
s
R/W
HR066
S
U049
User pump rotation time
12
0
999
h
R/W
HR067
S
U050
User side frost protection: alarm threshold
-0.8
-99.9
999.9
°C/°F
R/W
HR068 (2R)
S
U051
User side frost protection: diff erential
30.0
0.0
999.9
K/R
R/W
HR070 (2R)
S
U052
User-side frost protection: delay time at 1K
30
0
999
s
R/W
HR072
S
U053
Unit OFF: frost protection set point
4.0
-99.9
999.9
°C/°F
R/W
HR073 (2R)
S
U054
Unit OFF: frost protection diff erential
2.0
0.0
99.9
K/R
R/W
HR075 (2R)
S
U055
User side return temp. probe: off set
0.0
-99.9
99.9
K/R
R/W
HR079 (2R)